{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FL065","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FL065","canonicalUrl":"https://aoctrl.com/schneider/LX1FL065","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FL065","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1FL065 contactor coil, 65 V AC 50/60 Hz, without built-in suppressor module, 5 Mcycles mechanical durability.","salesMarkdown":"It is a bare coil without a built-in suppressor module, so you will need to add an external RC snubber or varistor across the coil terminals if driving it from a PLC output or solid-state relay — the lack of internal suppression means the inductive kickback lands on whatever switches it. Rated for 5 Mcycles mechanical durability and a maximum operating rate of 1200 cycles per hour at 55 °C, this coil is sized for continuous-duty applications like conveyor control or pump panels where the contactor cycles at a moderate pace. The AC control circuit draws from a 65 V supply — verify your control transformer taps before committing the BOM line, as a mis-matched coil voltage is a common field fault that delays commissioning. ## Sourcing reality — obsolete, quoted to order Schneider has marked the LX1FL065 as obsolete. No official successor order code exists, so this is a last-time-buy or surplus-channel part. If you are at the design stage, consider whether a 65 V AC control circuit is still the right choice for the panel. ## Integration note — panel fit and wiring The LX1FL coil snaps onto the TeSys F contactor magnet assembly — no tools needed for the coil swap, but the contactor must be de-energised and the arc chamber removed to access the coil retainer. Standard DIN-rail or screw-panel mount for the contactor itself; the coil adds no extra footprint. Wire the coil terminals to the 65 V AC control bus. Because the coil lacks a built-in suppressor, plan for a separate RC snubber across the coil terminals if the control signal comes from a PLC or proximity switch.","metaTitle":"Schneider LX1FL065 TeSys Contactor Coil, 65 V AC 50/60 Hz","metaDescription":"Obsolete LX1FL065 TeSys contactor coil, 65 V AC 50/60 Hz control circuit, 5 Mcycles mechanical durability. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1FL","Control circuit type":"AC 50/60 Hz","Mechanical durability":"5 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"1200 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"65 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f40a74e77a624feeaea2a8dc515d7201.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX1FL065/contactor-coil-lx1f-65-v-ac-50-60-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1FL065/alternatives.json"},"ai":{"faq":[{"question":"What is the control voltage and frequency for this coil?","answer":"The LX1FL065 is rated for 65 V AC at 50/60 Hz. It is an AC control circuit coil, not compatible with DC control voltages."},{"question":"Does this coil include a built-in suppressor?","answer":"No. The LX1FL065 is specified as 'without built-in suppressor module'. An external RC snubber or varistor must be added across the coil terminals when switching with electronic outputs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FL065","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FL065 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}