{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1FL075","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1FL075","canonicalUrl":"https://aoctrl.com/schneider/LX1FL075","factsUrl":"https://aoctrl.com/api/mcp/products/LX1FL075","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1FL075 contactor coil, 75 V AC 50/60 Hz, without built-in suppressor module.","salesMarkdown":"It is the control-circuit component that pulls the contactor armature in — no built-in suppressor module, so you add the RC snubber or varistor externally per the panel design. That rate governs pick-and-place or rapid-cycling applications — a conveyor jog station, for instance, stays within tolerance; a high-speed packaging line may need to check dwell time. The 75 V AC coil voltage is specific — not a 110 V or 230 V common tap. If your control transformer or control circuit bus is 75 V AC (common in some 50 Hz legacy panels or step-down schemes), this is the correct drop-in. The 50/60 Hz rating means it works on either line frequency, but the coil impedance changes slightly; the pull-in and hold-in power are designed for both. The TeSys range designation confirms it mates with the LX1F contactor platform — same mounting footprint, same auxiliary contact interface. No adapter bracket needed.","metaTitle":"Schneider Electric LX1FL075 TeSys contactor coil, 75 V AC 50","metaDescription":"Schneider Electric LX1FL075 TeSys contactor coil, 75 V AC 50/60 Hz control circuit. Active production. 5 Mcycles mechanical durability. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX1FL075","Category":"22341-CONTACTOR,D,K,&F ACCESS","description":"contactor coil - LX1F - 75 V AC - 50/60 Hz","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX1FL","Control circuit type":"AC 50/60 Hz","Mechanical durability":"5 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"1200 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"75 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/103e464613d524196abcd777ebdba3d1.pdf","sourceUrl":"https://www.se.com/th/en/product/LX1FL075/contactor-coil-lx1f-75-v-ac-50-60-hz/"},"ai":{"faq":[{"question":"What is the control circuit voltage and frequency for this coil?","answer":"The coil is rated 75 V AC at 50/60 Hz. It is designed for AC control circuits only, not DC."},{"question":"Does this coil include a built-in suppressor module?","answer":"No, the LX1FL075 is specified without a built-in suppressor module. An external RC snubber or varistor must be added across the coil terminals if suppression is required for your control circuit."},{"question":"What is the mechanical durability rating?","answer":"The coil is rated for 5 million mechanical cycles, with a maximum operating rate of 1200 cycles per hour at 131 °F (55 °C)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1FL075","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1FL075 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}