{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1G3RKUEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1G3RKUEN","canonicalUrl":"https://aoctrl.com/schneider/LX1G3RKUEN","factsUrl":"https://aoctrl.com/api/mcp/products/LX1G3RKUEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys LX1G3RKUEN contactor coil module, 100–250 V AC/DC control circuit, 3.7 in depth, built-in bidirectional peak limiting.","salesMarkdown":"The LX1G3RKUEN is a Schneider TeSys contactor coil module — the control-side component that drives the main contactor armature. It accepts a 100…250 V AC/DC control supply (50/60 Hz), with built-in bidirectional peak limiting that suppresses back-EMF and reduces radiated noise on the control wiring. That peak-limiting circuit means you don't need an external snubber for coil suppression, simplifying panel wiring and reducing parts count. ## Coil power and thermal headroom Inrush draws 645 W DC or 840 VA at 240 V AC, 60 Hz, then drops to a 5.9 W DC / 10.6 VA hold-in — a typical ratio for large contactor coils. That inrush transient matters for control transformer sizing: if you're feeding multiple coils from a single 240 VA transformer, sequence the closure to avoid sag. Hold power is modest, so continuous energization doesn't tax the supply. Ambient operating range is -13...140 °F (-25...60 °C). Storage range is -76...176 °F (-60...80 °C). Altitude derating starts above 9842.52 ft (3000 m); at 5000 m a derating factor applies. ## Physical fit and termination IP20 rated (finger-safe, no water ingress). Mechanical durability rated 5 million cycles; maximum operating rate 600 cycles/min at 140 °F (60 °C). For high-cycle applications (e.g., conveyor indexing), that rate is within spec.","metaTitle":"Schneider LX1G3RKUEN TeSys Contactor Coil, 100-250 V AC/DC","metaDescription":"Active Schneider LX1G3RKUEN TeSys contactor coil, 100-250 V AC/DC control circuit, 3.7 in depth, built-in peak limiting. Sourced to order. Cite E23, E1, L1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.7 in (93.0 mm)","Range":"TeSys","Width":"5.5 in (140.0 mm)","Height":"6.6 in (167.0 mm)","Category":"US10I1222328","Standards":"EN/IEC 60947-4-1 UL 60947-4-1A CSA C22.2 No 60947-4-1","Operating time":"20...35 ms opening 40...55 ms closing","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Pollution degree":"3 IEC 60947-1","Quantity per Set":"1","Device short name":"LX1G","Inrush power in W":"645.0 W DC","Poles description":"3P","Inrush power in VA":"840 VA 240 V AC, 60 Hz","Operating altitude":"9842.52 ft (3000 m) without derating 5000 m with derating factor","Mechanical durability":"5 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"600 cyc/mn 140 °F (60 °C)","Connections - terminals":"Control circuit push-in termination 1 0.0003...0.004 in² (0.2...2.5 mm²) solid stranded without cable end sleeve AWG 26...AWG 12 Control circuit push-in termination 1 0.0004...0.004 in² (0.25...2.5 mm²) flexible with cable end sleeve AWG 24...AWG 14 Control circuit push-in termination 2 0.0008...0.002 in² (0.5...1.0 mm²) rigid or stranded with cable end sleeve AWG 20...AWG 18","IP degree of protection":"IP20 IEC 60529","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"100...250 V AC/DC 50/60 Hz","Electromagnetic compatibility":"EMC immunity conforming to IEC 60947-4-1 Emission tests criteria A conforming to IEC 60947-4-1 Immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to SEMI F47","Control circuit voltage limits":"Operational 0.8...1.1 Uc 140 °F (60 °C)) Drop-out 0...0.45 Uc 140 °F (60 °C))","Hold-in power consumption in W":"5.9 W DC","Hold-in power consumption in VA":"10.6 VA 240 V AC, 60 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$357.45","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8994f54f5b78c2b38715061c7b453652.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1G3RKUEN/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of the LX1G3RKUEN?","answer":"The depth is 3.7 in (93.0 mm). That is the dimension from the mounting base to the front of the module."},{"question":"Does the LX1G3RKUEN comply with IEC and UL standards?","answer":"It is certified to EN/IEC 60947-4-1, UL 60947-4-1A, and CSA C22.2 No 60947-4-1. IP20 per IEC 60529."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1G3RKUEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1G3RKUEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}