{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1G3RLSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1G3RLSEN","canonicalUrl":"https://aoctrl.com/schneider/LX1G3RLSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LX1G3RLSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LX1G3RLSEN contactor coil, 200-500V AC/DC control voltage, 3-pole, built-in bidirectional peak limiting, IP20, active production.","salesMarkdown":"## Coil for LC1G265-330/3P — control voltage and mating pair The LX1G3RLSEN is the control module for the TeSys Giga LC1G265-330/3P standard contactor — it is not a standalone coil but the plug-on electronic control block that mates with those frame sizes. The 200...500 V AC/DC control circuit voltage covers both 240 V and 480 V control panels without a separate transformer tap. Built-in bidirectional peak limiting replaces the need for external varistor or RC snubber networks on the coil — the electronics handle the inductive kick internally, which simplifies panel wiring and reduces component count per starter. ## Power draw and thermal budget Inrush is 300 W / 530 VA for the 20...35 ms opening and 40...55 ms closing stroke; once sealed, hold-in drops to 9 W / 16.1 VA. That low sealed power means the coil runs cool inside a crowded enclosure — the 5 Mcycle mechanical durability rating is realistic at the rated 600 cycles/minute maximum at 140 °F (60 °C). Push-in terminals on the control circuit accept solid or stranded wire from AWG 26 to AWG 12 (0.2...2.5 mm²) without ferrules, or flexible with ferrules down to AWG 24. The dual termination points let you loop the control voltage through multiple coils without a separate terminal block. ## Standards and environmental limits Listed to EN/IEC 60947-4-1, UL 60947-4-1A, and CSA C22.2 No 60947-4-1 — the contactor standard for motor starters and controllers. Pollution degree 3 per IEC 60947-1 means it is rated for the conductive dust and humidity typical in industrial panels, not just clean-room environments. Operating altitude is 3000 m without derating, 5000 m with a derating factor. Ambient operation spans -25 °C to +60 °C, with storage from -60 °C to +80 °C. The IP20 finger-safe housing protects against accidental contact during maintenance. ## Sourcing and lifecycle Sourced to order against the BOM quantity through authorized distribution channels.","metaTitle":"Schneider LX1G3RLSEN Contactor Coil, TeSys Giga","metaDescription":"Active-production contactor coil for LC1G265-330/3P. 200-500V AC/DC control, built-in peak limiting, 5 Mcycles mechanical durability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.7 in (93.0 mm)","Width":"5.5 in (140.0 mm)","Height":"6.6 in (167.0 mm)","IP Rating":"IP20","Coil Voltage":"200...500 V AC/DC 50/60 Hz","Operating Time":"20...35 ms opening 40...55 ms closing","Product Status":"Active","Pollution Degree":"3 IEC 60947-1","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-76...176 °F (-60...80 °C)","Mechanical Life Cycles":"5 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"-13...140 °F (-25...60 °C)","Permissible Ambient Air Temperature Around The Device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$280.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0c292b564a38ff20c76ed0839e6b38ff.pdf","sourceUrl":"https://www.se.com/us/en/product/LX1G3RLSEN/control-module-tesys-giga-200500v-ac-dc-for-lc1g265330-3p-standard-version/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1G3RLSEN/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1G3RLSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1G3RLSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}