{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1LB080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1LB080","canonicalUrl":"https://aoctrl.com/schneider/LX1LB080","factsUrl":"https://aoctrl.com/api/mcp/products/LX1LB080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys LX1 coil, 80 V AC 50 Hz, 75 VA inrush / 8 VA sealed, 57.38 Ohm ±10%.","salesMarkdown":"The LX1LB080 is a replacement coil from Schneider's TeSys range, designed for 80 V AC 50 Hz control circuits. It's the spare part you order when the original coil on a TeSys contactor or starter fails, or when you're building a panel with a non-standard control voltage. Coil resistance is 57.38 Ohm at 20 °C ±10 % — that's the cold measurement. It determines the inrush current and the holding current the control transformer or PSU must deliver. The inrush power is 75 VA at 0.55 power factor (50 Hz); once sealed, it drops to 8 VA at 0.28 PF. That 9:1 ratio means the transformer must be sized for the inrush peak, not the sealed draw, or the voltage will sag and the contactor may chatter. Inductance is 0.95 mH — relevant if you're calculating the L/R time constant for suppression circuits or verifying compatibility with a PLC solid-state output driving the coil. Lifecycle status is active per Schneider, so this is a current-production part — no last-time-buy pressure. It's specified into the BOM line as a service spare (category 18402).","metaTitle":"Schneider LX1LB080 TeSys Coil, 80 V AC 50 Hz, 75 VA Inrush","metaDescription":"Schneider LX1LB080 TeSys coil, 80 V AC 50 Hz, 75 VA inrush / 8 VA sealed, 57.38 Ohm. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX1LB080","Category":"18402-WORLD SERVICE PARTS(CONTROL ACCESS)","description":"coil LX1-LB - 80 V AC 50Hz","lifecycle_stage":"current","Device short name":"LX1","Average resistance":"57.38 Ohm at 68 °F (20 °C) +/- 10 %","Value of inductance":"0.95 mH","Power consumption in VA":"75 VA AC 0.55 50 Hz inrush 8 VA AC 0.28 50 Hz sealed","Product or Component Type":"Coil","[Uc] control circuit voltage":"80 V AC 50 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/87fb8b1f62eac12736ffda01847ba51e.pdf","sourceUrl":"https://www.se.com/us/en/product/LX1LB080/coil-lx1lb-80-v-ac-50hz/"},"ai":{"faq":[{"question":"What control voltage does this coil need?","answer":"80 V AC at 50 Hz. Verify your panel supply matches before ordering — it's a less common voltage than 110 V or 230 V."},{"question":"What is the inrush and sealed VA?","answer":"75 VA inrush at 0.55 PF, 8 VA sealed at 0.28 PF. Size the control transformer for the inrush value."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1LB080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1LB080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}