{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1LB340","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1LB340","canonicalUrl":"https://aoctrl.com/schneider/LX1LB340","factsUrl":"https://aoctrl.com/api/mcp/products/LX1LB340","rawCanonicalId":null},"summary":{"shortDescription":"TeSys LX1LB340 replacement coil, 340V AC 50Hz / 380V AC 60Hz, 75VA inrush / 8VA sealed, 1060.99 Ohm ±10% at 20°C.","salesMarkdown":"The TeSys LX1LB340 is a replacement coil for TeSys contactors, not a complete contactor assembly. Coil draws 75 VA inrush at 0.55 power factor, dropping to 8 VA sealed at 0.28 power factor — the sealed hold power is what matters for continuous duty in a panel, keeping heat rise manageable inside the contactor enclosure. Rated coil resistance is 1060.99 Ohm ±10 % at 68 °F (20 °C). If you are bench-testing a contactor that chatters or fails to pull in, measuring resistance across the coil terminals against this value confirms whether the winding is open or shorted before you swap the part. Inductance is 6.6 H — this governs the magnetizing current and the time constant of the coil circuit. For a 50 Hz supply the inductive reactance is roughly 2 kΩ, which aligns with the sealed VA figure.","metaTitle":"TeSys LX1LB340 Coil, 340V AC 50Hz / 380V AC 60Hz","metaDescription":"TeSys LX1LB340 replacement coil for contactors. 340V AC 50Hz / 380V AC 60Hz control voltage, 75VA inrush / 8VA sealed. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"340 V AC 50 Hz 380 V AC 60 Hz","Product Status":"Active","Main Product Or Component Type":"Coil"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6089451aaef1a9f29229b4e6e825c9f3.pdf","sourceUrl":"https://www.se.com/us/en/product/LX1LB340/coil-lx1lb-340v-ac-50hz-380-v-ac-60hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1LB340/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1LB340","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1LB340 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}