{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1LC054","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1LC054","canonicalUrl":"https://aoctrl.com/schneider/LX1LC054","factsUrl":"https://aoctrl.com/api/mcp/products/LX1LC054","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1LC054 replacement coil, 54 V AC 50 Hz control circuit voltage, 9.215 Ohm ±10% resistance, 12-18 VA sealed power consumption, active production.","salesMarkdown":"The LX1LC054 is a TeSys-series replacement coil for a Schneider contactor or starter with a 54 V AC 50 Hz control circuit voltage. Coil resistance measures 9.215 Ohm ±10%, and the inductance is 0.107 mH with the magnetic circuit closed — meaning once the contactor pulls in, the holding current settles to a lower steady-state value. Inrush draws 170-230 VA at 0.55 power factor (60 Hz), dropping to 12-18 VA sealed at 0.3 PF. That inrush matters for the control transformer sizing; a 50 VA transformer won't reliably pick multiple coils simultaneously. ## What the category code tells you The category field reads '18402-WORLD SERVICE PARTS(CONTROL ACCESS)'. That's Schneider's internal service-parts classification — not a functional spec, but a signal that this part is stocked as a replaceable service item, not a one-off. For a storeroom manager, that means it's a known line item with established supply channels.","metaTitle":"Schneider Electric LX1LC054 TeSys Coil, 54 V AC 50 Hz, Activ","metaDescription":"Schneider Electric LX1LC054 TeSys replacement coil, 54 V AC 50 Hz control voltage, 9.215 Ohm resistance, 12-18 VA sealed. Active production. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX1LC054","Category":"18402-WORLD SERVICE PARTS(CONTROL ACCESS)","description":"coil LX1-LC - 54 V AC 50Hz,","lifecycle_stage":"current","Device short name":"LX1","Average resistance":"9.215 Ohm +/- 10 %","Value of inductance":"0.107 mH closed circuit","Power consumption in VA":"12...18 VA AC 0.3 60 Hz sealed 170...230 VA AC 0.55 60 Hz inrush","Product or Component Type":"Coil","[Uc] control circuit voltage":"54 V AC 50 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0684eeb3951ceb57ebe72d37800c7547.pdf","sourceUrl":"https://www.se.com/uk/en/product/LX1LC054/coil-lx1lc-54-v-ac-50hz/"},"ai":{"faq":[{"question":"What is the LX1LC054's listed range and category?","answer":"The range is TeSys. The category is 18402-WORLD SERVICE PARTS(CONTROL ACCESS), which is Schneider's internal service-parts classification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1LC054","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1LC054 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}