{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1LD020","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1LD020","canonicalUrl":"https://aoctrl.com/schneider/LX1LD020","factsUrl":"https://aoctrl.com/api/mcp/products/LX1LD020","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Integral replacement coil, LX1LD020, 24 V AC 60 Hz, 420-500 VA inrush, 0.213 Ohm resistance.","salesMarkdown":"The LX1LD020 is a replacement coil for the TeSys Integral line of combination starters — the part that pulls the contactor in when 24 V AC at 60 Hz is applied to the control circuit. It draws 420 to 500 VA inrush at 60 Hz with a 0.55 power factor, then settles to 24 to 36 VA holding power once the magnetic circuit closes. The coil resistance measures 0.213 Ohm at 68 °F (20 °C). Dropout occurs between 0.25 and 0.7 times Uc at temperatures up to 131 °F (55 °C). Because this is a replacement coil for a specific Integral starter frame, the physical fit (mounting holes, plunger stroke, terminal spacing) is fixed to that platform. No direct drop-in successor is listed in the official lifecycle record. A cross-reference search against the TeSys coil family is warranted if a new-production alternative is preferred. The 24 V AC 60 Hz control voltage is specific — not 50 Hz, not DC. If your panel supply is 24 V DC or 50 Hz mains, this coil will not pull in reliably or will overheat. The 420-500 VA inrush figure governs the control transformer sizing: a 50 VA transformer will drop voltage on pickup and may fail to close the contactor. Size the transformer for at least 500 VA momentary or use a dedicated control power supply. The hold-in power of 24-36 VA is the steady-state load the coil presents once sealed. This determines the thermal load on the control circuit and the rating of any pilot devices switching the coil.","metaTitle":"Schneider Electric LX1LD020 TeSys coil, 24 V AC 60 Hz, obsol","metaDescription":"LX1LD020 is a TeSys Integral replacement coil, 24 V AC 60 Hz, 420-500 VA inrush. Now obsolete; sourced to order against RFQ. Cross-reference available.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22384-STARTERS,INTEGRAL,ACCESS","lifecycle_stage":"current","Device short name":"LX1","Average resistance":"0.213 Ohm 68 °F (20 °C)","Inrush power in VA":"420...500 VA 60 Hz cos phi 0.55","Control circuit type":"AC 60 Hz","Nbr. of units in pkg.":"1","Product or Component Type":"Coil","Inductance of closed circuit":"0.045 H","[Uc] control circuit voltage":"24 V AC 60 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at Drop-out: 0.25...0.7 Uc (at <131 °F (55 °C))","Hold-in power consumption in VA":"24...36 VA 60 Hz cos phi 0.28"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/07f6df1b0b8eb1c9f03962f1945a00cf.pdf","sourceUrl":"https://www.se.com/nl/en/product/LX1LD020/tesys-integral-coil-24-v-ac-60-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1LD020/alternatives.json"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to LX1LD020?","answer":"No official direct replacement is listed in the lifecycle record. A cross-reference search against the TeSys coil family is needed to find a new-production coil with the same mounting and electrical characteristics."},{"question":"What is LX1LD020's listed range?","answer":"The LX1LD020 belongs to the TeSys range, Schneider Electric's line of motor control and protection components."},{"question":"What is LX1LD020's listed category?","answer":"The category is 22384-STARTERS,INTEGRAL,ACCESS — it is an accessory coil for integral combination starters."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1LD020","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1LD020 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}