{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1LD190","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1LD190","canonicalUrl":"https://aoctrl.com/schneider/LX1LD190","factsUrl":"https://aoctrl.com/api/mcp/products/LX1LD190","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX1LD190 replacement coil, 230-240 V AC 60 Hz control circuit, 420-500 VA inrush, 24-36 VA hold-in, for Integral starters.","salesMarkdown":"## What This Coil Does in the Panel The LX1LD190 is a replacement coil for Schneider Electric TeSys Integral starters, designed to pull in and hold the contactor armature on a 230-240 V AC 60 Hz control circuit. At inrush it draws 420-500 VA at 60 Hz with a 0.55 power factor — the surge is brief but the control transformer must be sized to deliver that without dropping below the 0.85 Uc dropout threshold. Once sealed, hold-in consumption drops to 24-36 VA at 0.28 power factor, with a closed-circuit inductance of 4.5 H and a DC resistance of 23.24 Ω at 20°C. ## Sourcing Reality — Obsolete, No Direct Successor Schneider lists the LX1LD190 as obsolete. For a BOM line that needs this exact coil, the only channel is independent surplus or broker stock. Availability is lot-specific and confirmed at RFQ; quantities are not held in regular distribution. If you are evaluating a board spin or panel redesign, the functional replacement is a different coil form factor — the LX1LD190's mounting and electrical interface are specific to the Integral platform, not the current TeSys island or TeSys GV series.","metaTitle":"Schneider LX1LD190 TeSys Integral Coil, 230-240 VAC 60 Hz","metaDescription":"Schneider Electric LX1LD190 TeSys replacement coil for integral starters. 230-240 VAC 60 Hz, 420-500 VA inrush, 24-36 VA hold. Obsolete, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"230...240 V AC 60 Hz","Product Status":"Active","Control Circuit Type":"AC 60 Hz","Main Product Or Component Type":"Coil"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/63eca1641cb72ce87b1d105df5fff8bb.pdf","sourceUrl":"https://www.se.com/ie/en/product/LX1LD190/tesys-integral-coil-230-240-v-ac-60-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1LD190/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1LD190","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1LD190 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}