{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX1LD360","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX1LD360","canonicalUrl":"https://aoctrl.com/schneider/LX1LD360","factsUrl":"https://aoctrl.com/api/mcp/products/LX1LD360","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Integral series, LX1LD360 replacement coil, 440 V AC 60 Hz control circuit, 420...500 VA inrush power.","salesMarkdown":"The LX1LD360 is a replacement coil from the TeSys Integral series, designed for 440 V AC 60 Hz control circuits. It pulls 420...500 VA inrush at 60 Hz with a 0.55 power factor, then settles to 24...36 VA hold-in at 0.28 power factor. The coil resistance measures 80.46 Ohm at 68 °F (20 °C). Operational voltage range is 0.85...1.1 Uc (374...484 V AC), with dropout at 0.25...0.7 Uc (110...308 V AC) at up to 131 °F (55 °C). This means the coil holds in reliably down to about 374 V and drops out cleanly below 110 V, preventing chatter on a sagging line.","metaTitle":"TeSys LX1LD360 Coil, 440 V AC 60 Hz, Obsolete","metaDescription":"TeSys LX1LD360 replacement coil for legacy contactors, 440 V AC 60 Hz control circuit. Obsolete; sourced to order against RFQ. 420-500 VA inrush, 24-36 VA hold-in.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"18402-WORLD SERVICE PARTS(CONTROL ACCESS)","lifecycle_stage":"current","Device short name":"LX1","Average resistance":"80.46 Ohm 68 °F (20 °C)","Inrush power in VA":"420...500 VA 60 Hz cos phi 0.55","Control circuit type":"AC 60 Hz","Nbr. of units in pkg.":"1","Product or Component Type":"Coil","Inductance of closed circuit":"16.7 H","[Uc] control circuit voltage":"440 V AC 60 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at Drop-out: 0.25...0.7 Uc (at <131 °F (55 °C))","Hold-in power consumption in VA":"24...36 VA 60 Hz cos phi 0.28"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ab2200db8580737de303d36d1eeb925a.pdf","sourceUrl":"https://www.se.com/th/en/product/LX1LD360/tesys-integral-coil-440-v-ac-60-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX1LD360/alternatives.json"},"ai":{"faq":[{"question":"What is the inrush and hold-in power consumption?","answer":"Inrush power is 420...500 VA at 60 Hz with a 0.55 power factor. Hold-in power drops to 24...36 VA at 60 Hz with a 0.28 power factor."},{"question":"What product range does the LX1LD360 belong to?","answer":"It belongs to the Schneider Electric TeSys range, specifically the TeSys Integral series of motor starters and control components."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX1LD360","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX1LD360 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}