{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4D6KD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4D6KD","canonicalUrl":"https://aoctrl.com/schneider/LX4D6KD","factsUrl":"https://aoctrl.com/api/mcp/products/LX4D6KD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX4D6KD contactor coil, 96 V DC, 51.9 Ohm, 10 Mcycles mechanical durability, without built-in suppressor module.","salesMarkdown":"The Schneider Electric TeSys LX4D6KD is a replacement contactor coil for the LX1D6 contactor range, wound for 96 V DC control circuits. It carries a coil resistance of 51.9 Ohm at 68 °F (20 °C) and an inductance of 4.18 H when closed, which determines the inrush and hold current the control supply must deliver. Rated for a maximum operating rate of 3600 cycles per hour at 140 °F (60 °C), with mechanical durability rated at 10 million cycles. The ambient operating range spans 23 to 140 °F (-5 to 60 °C). This coil has no built-in suppressor module, so you must add an external flyback diode or RC snubber across the coil terminals when driven by a PLC or DC supply — the inductive kick at turn-off can damage solid-state outputs or create noise on the control bus. The 96 V DC variant is less common than 24 V or 48 V coils, so verify the control voltage matches your panel's DC bus before committing the line item.","metaTitle":"Schneider LX4D6KD TeSys contactor coil, 96 V DC","metaDescription":"Schneider Electric TeSys LX4D6KD contactor coil, 96 V DC, 51.9 Ohm, 10 Mcycles mechanical durability. Active lifecycle, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"96 V DC","Product Status":"Active","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...140 °F (-5...60 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/220dbb2b9e105a6dafde54dffd612497.pdf","sourceUrl":"https://www.se.com/th/en/product/LX4D6KD/coil-lx4d-96-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4D6KD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4D6KD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4D6KD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}