{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4D6LD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4D6LD","canonicalUrl":"https://aoctrl.com/schneider/LX4D6LD","factsUrl":"https://aoctrl.com/api/mcp/products/LX4D6LD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX4D6LD, contactor coil, 200 V DC, 51.9 Ohm at 68 °F (20 °C), without built-in suppressor module.","salesMarkdown":"The LX4D6LD is a replacement coil for the LX1D6 contactor in the TeSys range. It operates on a 200 V DC control circuit and draws its holding current through a 51.9 Ohm winding at 68 °F (20 °C). This is a bare coil — no built-in suppressor module. On a DC coil, the inductive kickback is higher than an AC equivalent, so you need an external free-wheeling diode or varistor across the coil terminals. Wire it with the cathode to the positive rail; reversed polarity shorts the diode and kills the drive transistor on the PLC output card. Rated for 200 V DC control voltage — this is the nominal pick-up and hold voltage. On a DC coil, the inrush current is limited only by the DC resistance, so the 51.9 Ohm winding draws about 3.85 A during pick-up before the armature seats and the inductance rises to 4.18 H. That rate is the mechanical limit — the contactor's electrical life at rated load will be lower. For high-duty applications like rapid cycling conveyors, check the contactor's electrical endurance curve against your load current. Ambient temperature range of -5 to 60 °C. Within a sealed panel near a drive or transformer, ambient can exceed 50 °C — this coil is rated to handle it. Below -5 °C, the coil's pick-up voltage may shift; the DC resistance drops with cold, increasing inrush current, but the magnetic circuit's reluctance also rises. Not recommended for freezer applications without pre-heating.","metaTitle":"Schneider TeSys LX4D6LD Contactor Coil, 200 V DC, 51.9 Ohm","metaDescription":"TeSys LX4D6LD replacement coil for LX1D6 contactors. 200 V DC control circuit, 51.9 Ohm resistance at 20°C, 10 Mcycles mechanical durability. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"200 V DC","Product Status":"Active","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...140 °F (-5...60 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/791473e1575dfd14f565ba99ba918633.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX4D6LD/coil-lx4d-200-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4D6LD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4D6LD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4D6LD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}