{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4D7PD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4D7PD","canonicalUrl":"https://aoctrl.com/schneider/LX4D7PD","factsUrl":"https://aoctrl.com/api/mcp/products/LX4D7PD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D contactor coil, LX4D7PD, 155 V DC standard, for 80 A contactor, DC standard control circuit, obsolete.","salesMarkdown":"The LX4D7PD is a replacement contactor coil from the Schneider TeSys D range, designed for a 155 V DC standard control circuit and intended for use with an 80 A contactor. It is a DC standard coil without a built-in suppressor module, meaning the installer must provide external suppression — typically a free-wheeling diode across the coil — to manage the inductive kickback when the contactor drops out. The coil draws 22 W inrush and hold-in power at 68 °F (20 °C), with an average resistance of 1142.6 Ohm. The control circuit voltage limits are drop-out at 0.1...0.3 Uc and operational at 0.85...1.1 Uc, measured at up to 131 °F (55 °C). The time constant is 75 ms. The 155 V DC control voltage is specific — not a common 24 V DC or 110 V DC coil. If your panel's control transformer or DC bus supplies 155 V DC, this coil is a direct swap. If your supply is different, the coil will not pull in reliably (the operational range is 0.85 to 1.1 Uc, so 132 to 170 V DC). The mechanical durability of 10 Mcycles and a maximum operating rate of 3600 cycles per hour at 140 °F (60 °C) mean this coil is rated for moderate-duty cycling, not continuous high-speed pick-and-place.","metaTitle":"Schneider LX4D7PD TeSys contactor coil, 155 V DC, obsolete","metaDescription":"Schneider TeSys LX4D7PD replacement contactor coil, 155 V DC standard for 80 A contactor. Obsolete — sourced to order against RFQ. No built-in suppressor.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"155 V DC","Time Constant":"75 ms","Product Status":"Active","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"DC standard","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...140 °F (-5...60 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d32c3dfe6519ba8b89b9c5087f59b71b.pdf","sourceUrl":"https://www.se.com/uk/en/product/LX4D7PD/tesys-d-contactor-coil-lx4d7-155-v-dc-standard-for-80-a-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4D7PD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4D7PD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4D7PD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}