{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4FF022","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4FF022","canonicalUrl":"https://aoctrl.com/schneider/LX4FF022","factsUrl":"https://aoctrl.com/api/mcp/products/LX4FF022","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys range, LX4FF022 contactor coil, 22 V DC, 30-40 ms closing, 30-50 ms opening, 0.88 Ohm inrush resistance.","salesMarkdown":"The LX4FF022 is a replacement contactor coil from the Schneider Electric TeSys range, designed to fit FF-frame contactors. It operates on a 22 V DC control circuit, with a closing time of 30 to 40 ms and an opening time of 30 to 50 ms. The coil draws a 0.88 Ohm inrush resistance at 68 °F (20 °C) and holds at 159 Ohm at the same temperature. The 22 V DC control voltage is a wide-range DC type. Operational limits are 0.85 to 1.1 times Uc at 131 °F (55 °C). Drop-out occurs between 0.15 and 0.2 Uc at 131 °F (55 °C). This coil is a service part for TeSys FF contactors, which are DIN-rail or panel-mount devices common in motor control centers and distribution panels.","metaTitle":"TeSys LX4FF022 Contactor Coil, 22 V DC, Obsolete","metaDescription":"TeSys LX4FF022 contactor coil for FF contactors, 22 V DC control voltage. Now obsolete — sourced to order against an RFQ. Operating time 30-40 ms close, 30-50 ms open.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"18401-WORLD SERVICE PARTS(CTR ACCESS)","Operating time":"30...40 ms closing 30...50 ms opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX4FF","Average resistance":"0.88 Ohm inrush 68 °F (20 °C) 159 Ohm holding 68 °F (20 °C)","Control circuit type":"DC wide range","Nbr. of units in pkg.":"1","Maximum operating rate":"60 cyc/h 131 °F (55 °C)","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"22 V DC","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 131 °F (55 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b90f7fdd95ee7f8ff0ff0b9d8adb19f.pdf","sourceUrl":"https://www.se.com/th/en/product/LX4FF022/contactor-coil-ff-22-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4FF022/alternatives.json"},"ai":{"faq":[{"question":"What is the TeSys range for this coil?","answer":"The LX4FF022 belongs to the Schneider Electric TeSys range, which is a broad family of motor control and protection components including contactors, overload relays, and accessories."},{"question":"What is the category for this part?","answer":"It is listed under category 18401-WORLD SERVICE PARTS (CTR ACCESS), indicating it is a service/replacement part for contactor accessories."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4FF022","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4FF022 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}