{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4FH250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4FH250","canonicalUrl":"https://aoctrl.com/schneider/LX4FH250","factsUrl":"https://aoctrl.com/api/mcp/products/LX4FH250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, LX4FH250, 250 V DC control circuit, obsolete.","salesMarkdown":"The LX4FH250 is a DC low-consumption contactor coil from the TeSys F range, designed to fit the corresponding TeSys F contactor frame. Rated for a 250 V DC control circuit, it pulls in at 750 W inrush and holds at 5 W, with an average inrush resistance of 84 Ohm and a holding resistance of 13900 Ohm at 68 °F (20 °C). Closing time runs 40 to 50 ms; opening time is 40 to 65 ms. The 250 V DC coil is the key fit parameter — it is not a universal AC/DC coil. If your panel runs a 250 V DC control bus, this coil matches directly. The 0.85 to 1.1 Uc operational voltage range (212.5 to 275 V DC at 131 °F) gives some margin on a nominal 250 V bus, but the drop-out band of 0.15 to 0.2 Uc (37.5 to 50 V DC) means the contactor drops out cleanly on a low-voltage condition. The coil has no built-in suppressor module, so you will need an external flyback diode or RC snubber across the coil terminals to protect your DC control circuit from inductive kickback. Mounts onto the TeSys F contactor base. The DC low-consumption design keeps thermal rise in the panel lower than an AC coil running through a rectifier — relevant if the contactor is in a sealed enclosure with limited airflow. Inductance of the closed circuit is 1910 H, which governs the inrush current profile and the sizing of any external suppression circuit.","metaTitle":"TeSys LX4FH250 contactor coil, 250 V DC, obsolete","metaDescription":"Obsolete TeSys F contactor coil LX4FH250, 250 V DC control circuit. 40-50 ms closing, 10 Mcycles mechanical durability. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"250 V DC","Operating Time":"40...50 ms closing 40...65 ms opening","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"DC low consumption","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9f81da47f41cde658fb6e966c191bef8.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX4FH250/tesys-f-contactor-coil-lx4fh-250-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4FH250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4FH250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4FH250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}