{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4FH375","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4FH375","canonicalUrl":"https://aoctrl.com/schneider/LX4FH375","factsUrl":"https://aoctrl.com/api/mcp/products/LX4FH375","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, contactor coil, LX4FH375, 375 V DC, DC low consumption, 10 Mcycles mechanical durability.","salesMarkdown":"The LX4FH375 is a replacement coil for TeSys F contactors, wound for 375 V DC control. It is a DC low-consumption coil without a built-in suppressor module, so you will need to add a free-wheeling diode or RC snubber across the coil terminals if the driving PLC or relay card does not already handle flyback suppression. The coil draws 750 W inrush at 20 °C (about 2 A peak) and settles to 5 W holding. The holding resistance is 44 kΩ, which means the steady-state current is around 8.5 mA — low enough that a standard 24 V DC relay output can drive it through a series resistor or a dedicated DC coil driver, but the inrush spike needs a supply that can deliver the peak without droop. ## Timing and mechanical life Closing time is 40 to 50 ms; opening takes 40 to 65 ms. That spread matters if you are coordinating with upstream short-circuit protection or sequencing multiple contactors — the opening scatter can be 25 ms, so do not rely on this coil alone for precise simultaneous break. Maximum operating rate is 2400 cycles per hour at 55 °C. That is one cycle every 1.5 seconds — fine for most motor starting and resistive load switching, but if you are running a rapid-pick-and-place or a fast-reversing application, you will need to check the thermal rise in the coil. ## Voltage tolerance and temperature range The coil holds in from 0.85 to 1.1 times the rated control voltage (319 to 412 V DC) at 55 °C. Drop-out occurs between 0.15 and 0.2 Uc (56 to 75 V DC). That wide drop-out margin means the contactor will not chatter on a sagging DC bus — it stays pulled in until the voltage falls well below the nominal rail.","metaTitle":"TeSys LX4FH375 Contactor Coil, 375 V DC, Active","metaDescription":"TeSys F LX4FH375 contactor coil, 375 V DC control voltage, active lifecycle. 10 Mcycles mechanical durability, 40-50 ms closing time. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"375 V DC","Operating Time":"40...50 ms closing 40...65 ms opening","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"DC low consumption","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bf71ec31c78d98e6804497adc0972ef5.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX4FH375/tesys-f-contactor-coil-lx4fh-375-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4FH375/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4FH375","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4FH375 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}