{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4FJ075","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4FJ075","canonicalUrl":"https://aoctrl.com/schneider/LX4FJ075","factsUrl":"https://aoctrl.com/api/mcp/products/LX4FJ075","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor coil, 75 V DC control voltage, DC low consumption, without built-in suppressor module.","salesMarkdown":"The LX4FJ075 is a TeSys F replacement coil for DC-operated contactors, rated at 75 V DC control voltage and built for low-consumption DC control circuits. It has no built-in suppressor module, so you'll need to add a free-wheeling diode or RC snubber across the coil if the driving PLC card or relay doesn't already handle flyback suppression. Opening time runs 45–60 ms, closing time 50–60 ms — typical for a contactor this size. The holding resistance at 68 °F (20 °C) is 1321 ohms, with an inrush resistance of 5.05 ohms at the same temperature. That inrush-to-hold ratio is what the DC low-consumption design optimises for: high pull-in force without cooking the coil during continuous duty. The coil is rated for a control voltage of 75 V DC. Drop-out happens between 0.2 and 0.35 Uc (15 to 26 V DC) at 131 °F (55 °C); the operational range is 0.85 to 1.1 Uc (63.75 to 82.5 V DC) at the same temperature. If your DC supply sags below 64 V under load — say, during a simultaneous pickup of multiple contactors on a shared power supply — the coil may not pull in reliably. And if it drops below about 26 V, the contactor drops out, which could drop a motor or a heater load unexpectedly. Ambient operating temperature is rated from 23 to 131 °F (-5 to 55 °C).","metaTitle":"Schneider Electric LX4FJ075 TeSys Contactor Coil, 75 V DC","metaDescription":"LX4FJ075 is a TeSys F contactor coil for 75 V DC control circuits. Active production. Drop-out 0.2–0.35 Uc, operating 0.85–1.1 Uc. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"75 V DC","Operating Time":"45...60 ms opening 50...60 ms closing","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"DC low consumption","Main Product Or Component Type":"Contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2a97df7360f3e739703eebd0594685ae.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX4FJ075/contactor-coil-fj-75v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4FJ075/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4FJ075","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4FJ075 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}