{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4FK200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4FK200","canonicalUrl":"https://aoctrl.com/schneider/LX4FK200","factsUrl":"https://aoctrl.com/api/mcp/products/LX4FK200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys range, contactor coil LX4FK200, 200 V DC control voltage, 45-60 ms opening, 50-60 ms closing.","salesMarkdown":"The LX4FK200 is a contactor coil from the Schneider Electric TeSys range, designed to replace the coil in FK-series contactors. It operates on a 200 V DC control circuit with low-consumption DC coil technology. The coil pulls in with an inrush resistance of 35.4 Ω at 20 °C, then holds at 8649 Ω — the high holding resistance is what keeps power draw low once the contactor is sealed. Opening time is 45-60 ms, closing time 50-60 ms. ## Control voltage limits and operating range The coil is rated for 200 V DC nominal, with an operational range of 0.85 to 1.1 Uc at 55 °C. Drop-out occurs between 0.2 and 0.35 Uc at 55 °C. Ambient operating temperature is -5 to 55 °C. The coil ships without a built-in suppressor module — if your application needs flyback suppression, you add it externally. No direct replacement is published. Verify coil voltage and mechanical fit against the existing contactor frame.","metaTitle":"TeSys LX4FK200 Contactor Coil, 200 V DC, Obsolete","metaDescription":"TeSys LX4FK200 contactor coil, 200 V DC control voltage, 45-60 ms operating time. Obsolete — sourced to order against RFQ. Part of the TeSys range.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"18401-WORLD SERVICE PARTS(CTR ACCESS)","Operating time":"45...60 ms opening 50...60 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX4FK","Average resistance":"35.4 Ohm inrush 68 °F (20 °C) 8649 Ohm holding 68 °F (20 °C)","Control circuit type":"DC low consumption","Nbr. of units in pkg.":"1","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"200 V DC","Control circuit voltage limits":"Drop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ff70ebbe74d6f8b276d3e06990c47d64.pdf","sourceUrl":"https://www.se.com/us/en/product/LX4FK200/contactor-coil-fk-200-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX4FK200/alternatives.json"},"ai":{"faq":[{"question":"What is the control voltage and operating time?","answer":"The coil is rated for 200 V DC control voltage. Opening time is 45-60 ms, closing time is 50-60 ms."},{"question":"Does this coil include a built-in suppressor?","answer":"No. The LX4FK200 is listed as 'Without built-in suppressor module'. External flyback suppression must be added if required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4FK200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4FK200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}