{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX4FL200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX4FL200","canonicalUrl":"https://aoctrl.com/schneider/LX4FL200","factsUrl":"https://aoctrl.com/api/mcp/products/LX4FL200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LX4FL200, FK contactor coil, 200 V DC, without built-in suppressor module.","salesMarkdown":"The LX4FL200 is a TeSys FK contactor coil designed for 200 V DC control circuits. It is a service part (category 18401) for replacing or populating the coil on a compatible TeSys contactor frame. Opening time is 40 to 50 ms; closing time is 60 to 70 ms — a consistent, narrow band that matters when sequencing contactors in a motor starter or transfer scheme. ## Control voltage and dropout behaviour Rated control circuit voltage is 200 V DC. The coil drops out between 0.2 and 0.35 Uc at 131 °F (55 °C), and operates reliably from 0.85 to 1.1 Uc at the same temperature. That means the dropout threshold is well below the nominal hold level, giving a clean break without chatter. The coil has no built-in suppressor module. If the control circuit drives inductive loads or long wiring runs, an external flyback diode or RC snubber across the coil terminals is needed to protect the DC supply and limit EMI.","metaTitle":"Schneider Electric LX4FL200 TeSys contactor coil, 200 V DC","metaDescription":"Active TeSys contactor coil, 200 V DC control, 40-50 ms open / 60-70 ms close. No built-in suppressor. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX4FL200","Category":"18401-WORLD SERVICE PARTS(CTR ACCESS)","description":"contactor coil - FK - 200 V DC","Operating time":"40...50 ms opening 60...70 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Device short name":"LX4FL","Control circuit type":"DC low consumption","Nbr. of units in pkg.":"1","Product or Component Type":"Contactor coil","[Uc] control circuit voltage":"200 V DC","Control circuit voltage limits":"Drop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7a40e79ecd77cfd07fe22d3b23de7a60.pdf","sourceUrl":"https://www.se.com/th/en/product/LX4FL200/contactor-coil-fk-200-v-dc/"},"ai":{"faq":[{"question":"What is the control voltage and what are the dropout/operational limits?","answer":"The coil is rated for 200 V DC control. Dropout occurs between 0.2 and 0.35 Uc (40 to 70 V DC) at 55 °C; operational range is 0.85 to 1.1 Uc (170 to 220 V DC) at 55 °C."},{"question":"Does this coil include a built-in suppressor?","answer":"No — the coil is supplied without a built-in suppressor module. An external diode or RC snubber should be added if the control circuit requires transient suppression."},{"question":"What are the opening and closing times?","answer":"Opening time is 40 to 50 ms; closing time is 60 to 70 ms."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX4FL200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX4FL200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}