{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FF065","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FF065","canonicalUrl":"https://aoctrl.com/schneider/LX9FF065","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FF065","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LX9FF065, specific contactor coil, 65 V AC 40-400 Hz low consumption, obsolete status.","salesMarkdown":"The LX9FF065 is a specific replacement coil for the TeSys F contactor range, wound for 65 V AC 40-400 Hz control circuits. It's a low-consumption design — inrush pulls 690-855 VA at 20 °C, then drops to 6.6-8.1 VA holding, with coil resistance settling at 152.2 Ω once sealed. Opening time is 130 ms, closing 35 ms, which is standard for this frame size. This is the coil only — no built-in suppressor module, so you'll need to add a varistor or RC snubber across the terminals if driving it from a PLC output or solid-state relay. The heat dissipation runs 5.9-7.2 W, so check for adequate ventilation inside the enclosure if multiple contactors are ganged. This part is marked obsolete by Schneider. That's a solid service life for a contactor coil — the obsolescence isn't driven by wear-out, just Schneider's platform migration. The 65 V AC control voltage is the first thing to verify — this is not a 24 V or 110 V coil. It operates between 0.85 and 1.1 Uc (55.25-71.5 V AC) and drops out between 0.35 and 0.55 Uc (22.75-35.75 V AC). If your control transformer is putting out 48 V or 120 V, this coil won't pull in reliably or will burn up. The inrush VA figure (690-855 VA) matters for transformer sizing — a 100 VA control transformer won't handle the inrush of this coil plus others pulling in simultaneously.","metaTitle":"Schneider LX9FF065 TeSys F Contactor Coil, 65 VAC, Obsolete","metaDescription":"Schneider LX9FF065 TeSys F specific contactor coil, 65 V AC 40-400 Hz low consumption. Obsolete status; sourced to order against RFQ. 130 ms opening, 35 ms closing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"130 ms opening 35 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"5.9...7.2 W","Device short name":"LX9FF","Average resistance":"4.93 Ohm inrush 68 °F (20 °C) 152.2 Ohm holding 68 °F (20 °C)","Inrush power in VA":"690...855 VA 40...400 Hz (at 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Specific contactor coil","[Uc] control circuit voltage":"65 V AC 40...400 Hz","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 131 °F (55 °C))","Hold-in power consumption in VA":"6.6...8.1 VA 40...400 Hz (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5ebd0805441b77df7a3144a01d1a1db8.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX9FF065/tesys-f-specific-contactor-coil-65-v-ac-40-400-hz-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FF065/alternatives.json"},"ai":{"faq":[{"question":"What is LX9FF065's listed range?","answer":"It belongs to the TeSys F range of contactors and accessories from Schneider Electric."},{"question":"What is LX9FF065's category?","answer":"The category is 22341-CONTACTOR,D,K,&F ACCESS, which covers contactors and their accessories in the D, K, and F frame sizes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FF065","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FF065 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}