{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FF090","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FF090","canonicalUrl":"https://aoctrl.com/schneider/LX9FF090","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FF090","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, specific contactor coil, LX9FF090, 90 V AC 40..400 Hz low consumption, 10 Mcycles mechanical durability.","salesMarkdown":"The TeSys LX9FF090 is a specific contactor coil for the TeSys F range, designed to replace or service the coil on a TeSys F contactor frame. It operates on a 90 V AC control circuit at 40 to 400 Hz, with low-consumption AC coil technology — no built-in suppressor module, so you add your own RC snubber or varistor across the coil if the application needs one. Opening time is 130 ms, closing time 35 ms. The coil draws 690 to 855 VA inrush at 20 °C, then holds at 6.6 to 8.1 VA. Average resistance is 9.34 Ω inrush and 285.1 Ω holding at 20 °C. Heat dissipation runs 5.9 to 7.2 W. The control voltage limits are 0.85 to 1.1 Uc for operation and 0.35 to 0.55 Uc for drop-out at 55 °C. This part is listed as Obsolete by the manufacturer. No official successor order code exists.","metaTitle":"TeSys LX9FF090 Contactor Coil, 90 V AC, Obsolete","metaDescription":"TeSys F LX9FF090 specific contactor coil, 90 V AC 40-400 Hz low consumption. Obsolete — sourced to order against an RFQ. 10 Mcycles mechanical durability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"130 ms opening 35 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"5.9...7.2 W","Device short name":"LX9FF","Average resistance":"9.34 Ohm inrush 68 °F (20 °C) 285.1 Ohm holding 68 °F (20 °C)","Inrush power in VA":"690...855 VA 40...400 Hz (at 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Product or Component Type":"Specific contactor coil","[Uc] control circuit voltage":"90 V AC 40...400 Hz","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 131 °F (55 °C))","Hold-in power consumption in VA":"6.6...8.1 VA 40...400 Hz (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79cf630be581cdc6d7184b4d0fad854e.pdf","sourceUrl":"https://www.se.com/us/en/product/LX9FF090/tesys-f-specific-contactor-coil-90-v-ac-40-400-hz-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FF090/alternatives.json"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to LX9FF090 in this component family?","answer":"The manufacturer has not published a direct successor order code for this coil. A pin-compatible alternative would need to match the TeSys F contactor frame and the 90 V AC coil voltage — verify the mounting and electrical interface against your existing contactor before ordering any substitute."},{"question":"What is LX9FF090's listed range on this component line?","answer":"It belongs to the TeSys range."},{"question":"What is LX9FF090's listed category?","answer":"The category is 22341-CONTACTOR,D,K,&F ACCESS."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FF090","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FF090 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}