{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FH0362","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FH0362","canonicalUrl":"https://aoctrl.com/schneider/LX9FH0362","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FH0362","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F specific contactor coil, 36 V AC 40-400 Hz low consumption, LX9FH0362.","salesMarkdown":"The LX9FH0362 is a specific contactor coil from the TeSys F range, designed for 36 V AC control circuits at 40-400 Hz. It is a low-consumption coil without a built-in suppressor module, meaning you need to add external suppression (RC snubber or varistor) across the coil terminals if driving it from a PLC output or electronic controller — the lack of internal suppression means the coil's inductive kickback is unmanaged until you add it. The coil pulls 560-660 VA inrush at 68 °F (20 °C) across 40-400 Hz, then settles to 8-10 VA holding. That inrush current matters for transformer sizing in the control panel — a 36 V control transformer must handle the momentary surge without dropping below 0.85 Uc (30.6 V) or the coil may chatter on pickup. The holding power is modest, so continuous heat dissipation runs 8.4-10.4 W; in a densely packed panel, that adds up but is manageable with basic ventilation. Opening time is 25 ms, closing time 45 ms. That's typical for a contactor coil of this size — fast enough for motor starting but not for high-speed switching. The control circuit is AC low-consumption type, with operational limits of 0.85-1.1 Uc (30.6-39.6 V) at 131 °F (55 °C) and dropout at 0.35-0.55 Uc (12.6-19.8 V). The wide dropout margin means the coil releases reliably even on a sagging control supply — useful if your panel shares a transformer with other loads. Coil resistance measures 1.88 ohms inrush and 41.8 ohms holding at 68 °F (20 °C). The inrush resistance is essentially the DC resistance of the copper winding before the armature moves; once the contactor seals, the holding resistance rises as the magnetic circuit changes. This is normal for AC-operated contactor coils.","metaTitle":"TeSys LX9FH0362 contactor coil, 36 V AC, obsolete","metaDescription":"TeSys LX9FH0362 specific contactor coil, 36 V AC 40-400 Hz low consumption. Obsolete — sourced to order against RFQ. Mechanical durability 10 Mcycles.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"25 ms opening 45 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"8.4...10.4 W","Device short name":"LX9FH","Average resistance":"1.88 Ohm inrush 68 °F (20 °C) 41.8 Ohm holding 68 °F (20 °C)","Inrush power in VA":"560...660 VA 40...400 Hz (at 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"3600 cyc/h 131 °F (55 °C)","Product or Component Type":"Specific contactor coil","[Uc] control circuit voltage":"36 V AC 40...400 Hz","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 131 °F (55 °C))","Hold-in power consumption in VA":"8...10 VA 40...400 Hz (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1b489ea70e2c6034da3e6f24ec4bf045.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX9FH0362/tesys-f-specific-contactor-coil-36-v-ac-40-400-hz-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FH0362/alternatives.json"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to LX9FH0362 in this component family?","answer":"The evidence does not list a direct pin-compatible replacement or successor order code. For a drop-in fit, you would need to source the original LX9FH0362 through surplus channels, or replace the entire contactor assembly with a current TeSys F coil and contactor set that matches your control voltage and mounting footprint."},{"question":"What is LX9FH0362's listed range?","answer":"It belongs to the TeSys range."},{"question":"What is LX9FH0362's listed category?","answer":"The category is 22341-CONTACTOR,D,K,&F ACCESS."},{"question":"What compliance documentation does this brand provide for LX9FH0362?","answer":"The evidence does not list specific compliance documentation such as RoHS, REACH, UL, or IEC certifications for this part."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FH0362","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FH0362 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}