{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FH0602","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FH0602","canonicalUrl":"https://aoctrl.com/schneider/LX9FH0602","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FH0602","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, specific contactor coil, LX9FH0602, 60 V AC 40-400 Hz low consumption, 25 ms opening / 45 ms closing, 10 Mcycles mechanical durability.","salesMarkdown":"The LX9FH0602 is a specific replacement coil for the TeSys F contactor range, wound for 60 V AC control at 40 to 400 Hz. It is a low-consumption variant, meaning the hold-in power drops to 8 to 10 VA once the contactor is sealed, versus the 560 to 660 VA inrush at pickup. That inrush figure matters for transformer sizing in the control circuit — a 60 VA control transformer will not support this coil on its own; plan for the inrush peak. The 25 ms opening time and 45 ms closing time are the mechanical stroke durations at rated voltage. For a safety circuit timing study, the opening time is the relevant number — it defines how fast the main poles break under fault conditions. The closing time governs how quickly the contactor can re-energize a load after a momentary dip. ## Control circuit and suppressor note The coil is delivered without a built-in suppressor module. That means the end user must add an external RC snubber or varistor across the coil terminals if the control circuit contains solid-state outputs or PLC relay modules. Without suppression, the inductive kick from the coil at drop-out can exceed 1 kV — enough to damage a 24 V DC output card sharing the same panel. The datasheet's recommended suppressor part number is not listed here, but any standard 60 V AC RC suppressor rated for the coil's VA will work. Verify free-wheel diode polarity if using a DC-suppressed circuit on an AC coil — a diode will short the AC half-cycle. ## Thermal and mechanical limits Heat dissipation runs 8.4 to 10.4 W once the coil is sealed. In a densely packed panel with multiple TeSys F contactors side by side, that thermal load adds up — allow for natural convection or forced airflow if the ambient inside the enclosure exceeds 40 °C. The rated operating range is -5 to 55 °C ambient; the mechanical durability is 10 million cycles, and the maximum operating rate is 3600 cycles per hour at 55 °C. That rate is achievable only with the coil at full rated voltage and the contactor unloaded — derate for motor switching duty.","metaTitle":"TeSys LX9FH0602 Specific Contactor Coil, 60 V AC 40-400 Hz","metaDescription":"TeSys F LX9FH0602 specific contactor coil, 60 V AC 40-400 Hz low consumption. Active production. 25 ms opening, 45 ms closing. 10 Mcycles mechanical durability. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX9FH0602","description":"TeSys F - specific contactor coil - 60 V AC 40..400 Hz low consumption","Operating time":"25 ms opening 45 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"8.4...10.4 W","Device short name":"LX9FH","Average resistance":"4.79 Ohm inrush at 20 °C 100 Ohm holding at 20 °C","Inrush power in VA":"560...660 VA 40...400 Hz (at 20 °C)","Control circuit type":"AC at 40...400 Hz low consumption","Mechanical durability":"10 Mcycles","Maximum operating rate":"3600 cyc/h 55 °C","Product or component type":"Specific contactor coil","[Uc] control circuit voltage":"60 V AC 40...400 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at 55 °C) Drop-out: 0.35...0.55 Uc (at 55 °C)","Hold-in power consumption in VA":"8...10 VA 40...400 Hz (at 20 °C)","Ambient air temperature for operation":"-5...55 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d7c043739a199dc20fb73c7cd22913d4.pdf","sourceUrl":"https://www.se.com/th/en/product/LX9FH0602/tesys-f-specific-contactor-coil-60-v-ac-40-400-hz-low-consumption/"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to LX9FH0602 in this component family?","answer":"Within the TeSys F range, the LX9FH coil family shares the same mechanical footprint and mounting dimensions. The difference is the control voltage — the LX9FH0602 is wound for 60 V AC. A 48 V AC or 110 V AC variant would require a different order code and would not be electrically interchangeable without changing the control transformer tap. No pin-compatible alternative with the same voltage exists in the family; the 60 V AC winding is specific to this code."},{"question":"What is LX9FH0602's listed range (TeSys) on this component line?","answer":"The LX9FH0602 belongs to the TeSys F range of contactors and motor starters. TeSys F is the heavy-duty, high-current series (up to 800 A in the contactor frame) used for motor switching, power distribution, and resistive loads in industrial control panels."},{"question":"What is LX9FH0602's listed operating time (25 ms opening 45 ms closing) on this component line?","answer":"The coil's mechanical operating time is 25 ms for opening (de-energizing the coil) and 45 ms for closing (energizing the coil). These are the stroke durations at rated voltage and 20 °C; the actual electrical arc extinction time will be longer depending on the load current and power factor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FH0602","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FH0602 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}