{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FH0652","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FH0652","canonicalUrl":"https://aoctrl.com/schneider/LX9FH0652","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FH0652","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F specific contactor coil, LX9FH0652, 65 V AC 40-400 Hz low consumption, 25 ms opening / 45 ms closing.","salesMarkdown":"The LX9FH0652 is a specific contactor coil from the TeSys F range, designed to replace or service the coil assembly on a TeSys F contactor frame. It's a drop-in service part, not a standalone component — you're buying the electromagnet that pulls the contactor in. Rated for 65 V AC at 40-400 Hz, low-consumption type. That 65 V is the nominal pick-up voltage; the coil holds in at 85-110% of Uc and drops out between 35-55% of Uc, both at 55 °C. If your control transformer is feeding a nominal 65 V bus, this coil tracks it. If you're on a 48 V or 110 V control scheme, this isn't the one. Opening time is 25 ms, closing time 45 ms. That's fast enough for most motor starting and general switching duty on a line. ## Coil characteristics and thermal budget This coil draws 560-660 VA inrush at 20 °C, then settles to 8-10 VA holding. The inrush-to-hold ratio is steep — about 60:1 — which is typical for AC-operated contactor coils. The heat dissipation is 8.4 to 10.4 W once sealed. That's not trivial in a crowded panel; if you're grouping several TeSys F contactors side by side, factor that thermal load into your enclosure sizing or you'll cook the coil. Coil resistance: 5.99 ohms inrush at 20 °C, 127 ohms holding at 20 °C. No built-in suppressor module, so you'll need an external RC snubber or varistor across the coil if you're switching it with a PLC output or a solid-state relay — otherwise the inductive kickback will eat your driver. The 55 °C ceiling is the coil's limit, not the contactor's.","metaTitle":"TeSys LX9FH0652 Contactor Coil, 65 V AC 40-400 Hz","metaDescription":"TeSys F specific contactor coil, 65 V AC 40-400 Hz low consumption. Active production. 25 ms opening, 45 ms closing. 10 Mcycles mechanical durability. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX9FH0652","description":"TeSys F - specific contactor coil - 65 V AC 40..400 Hz low consumption","Operating time":"25 ms opening 45 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"8.4...10.4 W","Device short name":"LX9FH","Average resistance":"5.99 Ohm inrush at 20 °C 127 Ohm holding at 20 °C","Inrush power in VA":"560...660 VA 40...400 Hz (at 20 °C)","Control circuit type":"AC at 40...400 Hz low consumption","Mechanical durability":"10 Mcycles","Maximum operating rate":"3600 cyc/h 55 °C","Product or component type":"Specific contactor coil","[Uc] control circuit voltage":"65 V AC 40...400 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at 55 °C) Drop-out: 0.35...0.55 Uc (at 55 °C)","Hold-in power consumption in VA":"8...10 VA 40...400 Hz (at 20 °C)","Ambient air temperature for operation":"-5...55 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/afddc8b67b4f58a0dc614e970f461efb.pdf","sourceUrl":"https://www.se.com/sg/en/product/LX9FH0652/tesys-f-specific-contactor-coil-65-v-ac-40-400-hz-low-consumption/"},"ai":{"faq":[{"question":"What is the operating time of this coil?","answer":"Opening time is 25 ms, closing time is 45 ms."},{"question":"What is the control voltage for LX9FH0652?","answer":"The control circuit voltage is 65 V AC at 40-400 Hz. It operates between 85% and 110% of Uc and drops out between 35% and 55% of Uc at 55 °C."},{"question":"Does this coil have a built-in suppressor?","answer":"No, the LX9FH0652 is supplied without a built-in suppressor module. An external RC snubber or varistor is recommended when switching with electronic outputs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FH0652","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FH0652 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}