{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FJ919","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FJ919","canonicalUrl":"https://aoctrl.com/schneider/LX9FJ919","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FJ919","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LX9FJ919 specific contactor coil, 50-56 V DC / 57-62 V AC 40-400 Hz, 60 ms opening / 20 ms closing, obsolete.","salesMarkdown":"It is not a general-purpose coil; it is designed to drop into the F-frame contactor's magnetic circuit and is rated for the mechanical duty cycle of that platform. Control voltage is 50...56 V DC or 57...62 V AC 40-400 Hz. The coil holds in at 0.85 to 1.1 Uc at 55 °C and drops out between 0.3 and 0.5 Uc. Opening time is 60 ms, closing 20 ms. That asymmetry is typical for a large-frame contactor where the spring force for break is stiffer than the magnetic pull-in. The 3600 cycles/hour maximum at 70 °C means it can follow a fast-pulsing load profile, but for continuous high-rate applications like a welding gun you would want to check thermal rise against the 11.4 to 13.9 W heat dissipation. Mechanical durability is 10 Mcycles — that is the life of the coil's own plunger and return spring, not the contactor's main contacts. In a typical motor-start application cycling a few times an hour, that translates to decades of service. No built-in suppressor module means the coil's magnetic field collapses without internal damping. For a 500 VA inrush coil, that can generate a significant inductive kickback spike. If the control circuit uses a PLC output or solid-state relay, an external flyback diode (DC) or RC snubber (AC) across the coil terminals is recommended — the contactor's own aux contacts do not supply that protection. ## Deployment context The coil is a plug-in replacement accessed by removing the contactor's arc chute and magnet assembly.","metaTitle":"TeSys LX9FJ919 Contactor Coil, 50-56 VDC / 57-62 VAC, Obsole","metaDescription":"Schneider Electric TeSys F LX9FJ919 specific contactor coil, 50-56 VDC / 57-62 VAC control voltage. Obsolete — sourced to order against RFQ. 60 ms opening, 20 ms closing. No built-","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"50...56 V DC 57...62 V AC 40...400 Hz","Operating Time":"60 ms opening 20 ms closing","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Control Circuit Type":"AC 40...400 Hz low consumption DC low consumption","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Specific contactor coil","Ambient Air Temperature Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c229a99215cd22c511a52ac2296d52d4.pdf","sourceUrl":"https://www.se.com/th/en/product/LX9FJ919/specific-contactor-coil-tesys-f-lx9fj-temperature-70-c/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FJ919/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FJ919","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FJ919 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}