{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FJ927","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FJ927","canonicalUrl":"https://aoctrl.com/schneider/LX9FJ927","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FJ927","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, specific contactor coil, LX9FJ927, 125 V DC low consumption, 125 V AC, 60 ms opening, 20 ms closing, 10 Mcycles mechanical durability.","salesMarkdown":"## Part Identity and Key Specs The LX9FJ927 is a specific contactor coil from the TeSys F range, designed for use with TeSys F contactors. It operates on a 125 V control circuit, accepting both AC (40...400 Hz) and DC low-consumption supply. Coil opening time is 60 ms, closing time is 20 ms — these switching speeds matter for coordinating with upstream protection and PLC scan cycles. Control voltage limits are operational 0.85...1.1 Uc at 131 °F (55 °C), with drop-out at 0.3...0.5 Uc. This means the coil holds in reliably down to about 106 V on a 125 V nominal supply, and drops out cleanly below about 38 V — important for brownout ride-through and predictable de-energization. ## Integration Notes for Panel Builders This coil has no built-in suppressor module, so an external RC snubber or flyback diode must be added across the coil terminals when driven by a PLC output or solid-state relay. Without suppression, the inductive kick from the 2 H closed-circuit inductance can damage switching contacts or cause EMI issues on the control wiring. Heat dissipation runs 11.4...13.9 W during hold-in — enough to raise temperature inside a crowded enclosure. Allow adequate ventilation or derating when mounting multiple coils side-by-side in a panel. Maximum operating rate is 3600 cycles per hour at 158 °F (70 °C). For high-duty applications like rapid cycling conveyors or press controls, verify the duty cycle stays within this limit to avoid coil overheating.","metaTitle":"TeSys LX9FJ927 Contactor Coil, 125 V AC/DC, Obsolete","metaDescription":"TeSys F specific contactor coil LX9FJ927, 125 V AC/DC control voltage, obsolete status. Sourced to order against RFQ. Operating time 60 ms open, 20 ms close.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"60 ms opening 20 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"11.4...13.9 W","Device short name":"LX9FJ","Inrush power in W":"430 W 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption DC low consumption","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"3600 cyc/h 158 °F (70 °C)","Product or Component Type":"Specific contactor coil","Inductance of closed circuit":"2 H","[Uc] control circuit voltage":"125 V DC 125 V AC","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))","Hold-in power consumption in W":"22 W 68 °F (20 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4894d6c4592c96ea4b558cd2046167dd.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX9FJ927/tesys-f-specific-contactor-coil-125-v-dc-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FJ927/alternatives.json"},"ai":{"faq":[{"question":"What is the control voltage for this coil?","answer":"The LX9FJ927 operates on 125 V control voltage, accepting both AC (40...400 Hz) and DC low-consumption supply."},{"question":"What are the key timing specs for the LX9FJ927?","answer":"Opening time is 60 ms, closing time is 20 ms. Mechanical durability is rated at 10 million cycles."},{"question":"Does this coil include a built-in suppressor?","answer":"No, the LX9FJ927 is supplied without a built-in suppressor module. An external snubber or flyback diode is required for inductive load switching."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FJ927","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FJ927 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}