{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FK916","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FK916","canonicalUrl":"https://aoctrl.com/schneider/LX9FK916","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FK916","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F specific contactor coil, LX9FK916, 35..38 V DC low consumption, obsolete status.","salesMarkdown":"The TeSys LX9FK916 is a specific contactor coil for the TeSys F contactor range, designed to operate on a 35...38 V DC control circuit with low consumption. It draws an inrush power of 550 VA at 20 °C and holds in at 31 VA, with a heat dissipation of 15...18.3 W during continuous operation. The 35...38 V DC control voltage is the nominal operating band — the coil will pick up reliably between 0.85 and 1.1 Uc (roughly 30 to 42 V DC at 55 °C) and drops out between 0.3 and 0.5 Uc (about 10.5 to 19 V DC). That dropout margin is what keeps the contactor from chattering on a sagging 24 V bus. Opening time is 60 ms, closing 50 ms — fast enough for most motor start/stop sequences but not for high-speed jogging. The 3600 cycles/hour maximum at 70 °C matches typical conveyor or pump duty. For a BOM replacement, the closest functional match would be a TeSys F coil with the same 35...38 V DC rating and low-consumption design, but pinout and mounting footprint should be verified against the existing contactor. As a specific coil for the TeSys F range, it mounts directly onto the contactor's magnet system — no adapter plate needed. The coil technology is without built-in suppressor module, so if your circuit requires flyback suppression (e.g., PLC-driven outputs), you'll need an external RC snubber or diode across the coil terminals.","metaTitle":"TeSys LX9FK916 specific contactor coil, 35..38 V DC, obsolet","metaDescription":"TeSys LX9FK916 specific contactor coil for TeSys F contactors, 35..38 V DC, low consumption. Obsolete status – sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"60 ms opening 50 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"15...18.3 W","Device short name":"LX9FK","Inrush power in VA":"550 VA (at 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption DC low consumption","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"3600 cyc/h 158 °F (70 °C)","Product or Component Type":"Specific contactor coil","[Uc] control circuit voltage":"35...38 V DC","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))","Hold-in power consumption in VA":"31 VA (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/08deebc4d2c86e87b17ccb6e414fcb01.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX9FK916/specific-contactor-coil-tesys-f-35-38-v-dc-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FK916/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the LX9FK916?","answer":"No official successor order code is published. A functional alternative would be a TeSys F low-consumption coil rated for 35...38 V DC, but you must verify the pinout and mounting compatibility with your existing contactor."},{"question":"What is the control voltage range for the LX9FK916?","answer":"The nominal control voltage is 35...38 V DC. The operational range is 0.85 to 1.1 Uc (about 30 to 42 V DC at 55 °C), and dropout occurs between 0.3 and 0.5 Uc (about 10.5 to 19 V DC)."},{"question":"Does the LX9FK916 include a built-in suppressor module?","answer":"No, the coil technology is without built-in suppressor module. You will need to add external flyback suppression if driving it from a solid-state output."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FK916","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FK916 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}