{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FL922","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FL922","canonicalUrl":"https://aoctrl.com/schneider/LX9FL922","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FL922","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, specific contactor coil, LX9FL922, 110 V AC/DC control circuit, 60 ms opening / 20 ms closing, without built-in suppressor module.","salesMarkdown":"Heat dissipation runs 22.8...27.8 W — that is the continuous power the coil dumps into the panel when held in. In a densely packed TeSys F enclosure, that heat adds up; if you are grouping multiple contactors in a single cabinet, factor the dissipation into the thermal budget rather than relying on the contactor's own ventilation alone. Inrush power is 733 W at 68 °F (20 °C), which is the peak draw during the pickup transient before the coil's inductance rises. That pulse lasts only the 20 ms closing time, but it can sag a 24 V DC supply rail if the power supply is undersized for multiple simultaneous pickups. Hold-in power consumption settles to 48 W at the same temperature — the steady-state draw after the armature seals. That rate translates to one operation every two seconds, which is typical for a high-duty-cycle application like a press control or a fast-indexing conveyor — but at that rate the coil temperature will rise above the ambient, so the 158 °F limit is the coil's own internal temperature, not the cabinet ambient. The control circuit accepts AC 40...400 Hz or DC low-consumption drive. The 40 Hz lower bound means it works on 50 Hz and 60 Hz mains cleanly, and the 400 Hz upper bound covers aircraft or genset supplies. The DC low-consumption label means the coil is wound for a lower steady-state current than a standard DC coil — the 48 W hold-in confirms that — so it is compatible with electronic control outputs that cannot source a high continuous current. The LX9FL922 is a specific contactor coil — it mounts onto the TeSys F contactor frame, not a DIN-rail base. The coil itself is the replaceable element inside the contactor assembly; swapping it changes the control voltage without replacing the entire contactor.","metaTitle":"TeSys LX9FL922 specific contactor coil, 110 V AC/DC","metaDescription":"TeSys F specific contactor coil LX9FL922, 110 V AC/DC control circuit, 60 ms opening / 20 ms closing, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","title":"LX9FL922","Category":"22341-CONTACTOR,D,K,&F ACCESS","description":"TeSys F - specific contactor coil","Operating time":"60 ms opening 20 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"22.8...27.8 W","Device short name":"LX9FL","Inrush power in W":"733 W 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption DC low consumption","Mechanical durability":"5 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"1800 cyc/h 158 °F (70 °C)","Product or Component Type":"Specific contactor coil","Inductance of closed circuit":"0.98 H","[Uc] control circuit voltage":"110 V DC 110 V AC","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))","Hold-in power consumption in W":"48 W 68 °F (20 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4a4432785a480ffbf8c43e2c573b6b12.pdf","sourceUrl":"https://www.se.com/th/en/product/LX9FL922/tesys-f-specific-contactor-coil/"},"ai":{"faq":[{"question":"What control voltage does the LX9FL922 accept?","answer":"The coil accepts 110 V AC or 110 V DC. The operational voltage range is 0.85...1.1 Uc (93.5...121 V) at 131 °F, and dropout occurs between 0.3...0.5 Uc (33...55 V) at the same temperature."},{"question":"Does the LX9FL922 include a built-in suppression module?","answer":"No, the coil technology is listed as without built-in suppressor module. An external free-wheeling diode or RC snubber must be added across the coil terminals when driven by a solid-state output to suppress the inductive flyback."},{"question":"What is the heat dissipation of the LX9FL922 coil?","answer":"The continuous heat dissipation is 22.8...27.8 W when the coil is held in. Inrush power at pickup is 733 W at 68 °F, and hold-in power consumption is 48 W at the same temperature."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FL922","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FL922 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}