{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FL926","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FL926","canonicalUrl":"https://aoctrl.com/schneider/LX9FL926","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FL926","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, specific contactor coil, 127 V DC low consumption, LX9FL926.","salesMarkdown":"The LX9FL926 is a specific contactor coil from the TeSys F range, designed as a replacement coil for TeSys F contactors. It operates on a 127 V DC control circuit, with low-consumption AC 40...400 Hz and DC control circuit types. This coil has an opening time of 60 ms and a closing time of 20 ms, with a maximum operating rate of 1800 cycles per hour at 158 °F (70 °C). Mechanical durability is rated at 5 Mcycles. ## Electrical characteristics and thermal management The coil draws an inrush power of 733 W at 68 °F (20 °C), with an inrush resistance of 20.8 Ohm. Holding power at 68 °F (20 °C) is 48 W, with a holding resistance of 167 Ohm. Heat dissipation ranges from 22.8 to 27.8 W. Control circuit voltage limits are 0.85...1.1 Uc for operation and 0.3...0.5 Uc for drop-out at 131 °F (55 °C). The coil does not include a built-in suppressor module, so external suppression is needed for inductive load switching. Inductance of the closed circuit is 1.2 H. Ambient air temperature for operation is 23...131 °F (-5...55 °C). The coil technology is without built-in suppressor module.","metaTitle":"TeSys LX9FL926 specific contactor coil, 127 V DC, obsolete","metaDescription":"TeSys F specific contactor coil, 127 V DC low consumption. Obsolete — sourced to order against RFQ. 60 ms opening, 20 ms closing. 5 Mcycles mechanical durability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"60 ms opening 20 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"22.8...27.8 W","Device short name":"LX9FL","Inrush power in W":"733 W 68 °F (20 °C))","Average resistance":"20.8 Ohm inrush 68 °F (20 °C) 167 Ohm holding 68 °F (20 °C)","Control circuit type":"AC 40...400 Hz low consumption DC low consumption","Mechanical durability":"5 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"1800 cyc/h 158 °F (70 °C)","Product or Component Type":"Specific contactor coil","Inductance of closed circuit":"1.2 H","[Uc] control circuit voltage":"127 V DC","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))","Hold-in power consumption in W":"48 W 68 °F (20 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4136022c7cf97ac3a2f89351989b9dcd.pdf","sourceUrl":"https://www.se.com/vn/en/product/LX9FL926/tesys-f-specific-contactor-coil-125-v-dc-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FL926/alternatives.json"},"ai":{"faq":[{"question":"What is the control voltage for this coil?","answer":"The control circuit voltage is 127 V DC, with operational limits of 0.85...1.1 Uc and drop-out limits of 0.3...0.5 Uc at 131 °F (55 °C)."},{"question":"What are the key electrical ratings for the LX9FL926?","answer":"Inrush power is 733 W at 68 °F (20 °C), holding power is 48 W at 68 °F (20 °C), and heat dissipation is 22.8...27.8 W. Opening time is 60 ms, closing time is 20 ms."},{"question":"How do I source the LX9FL926 if it is obsolete?","answer":"The LX9FL926 is sourced through the surplus and broker market. Submit an RFQ for current availability and pricing on remaining stock."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FL926","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FL926 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}