{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LX9FL936","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LX9FL936","canonicalUrl":"https://aoctrl.com/schneider/LX9FL936","factsUrl":"https://aoctrl.com/api/mcp/products/LX9FL936","rawCanonicalId":null},"summary":{"shortDescription":"TeSys F, specific contactor coil, LX9FL936, 415...440 V AC 40...400 Hz low consumption, 830 VA inrush, 47 VA holding.","salesMarkdown":"The LX9FL936 is a specific contactor coil from the TeSys F range, designed to pull in and hold a TeSys F contactor. It operates on a control circuit voltage of 415...440 V AC (40...400 Hz) or 415...440 V DC, with an inrush power draw of 830 VA at 20 °C and a hold-in consumption of 47 VA. The coil draws 1670 Ω holding resistance at 20 °C, and the closed-circuit inductance is 11 H. Opening time is 60 ms, closing time 50 ms. There is no built-in suppressor module, so you will need to add a free-wheeling diode or RC snubber across the coil terminals if driving it from a PLC output or solid-state relay. The 415...440 V AC/DC control voltage is the headline constraint: if your panel control supply is 480 V or 240 V, this coil will not pick up or may overheat. The operational voltage limits are 0.85...1.1 Uc at 55 °C, so the coil holds the contactor closed down to about 353 V and picks up reliably above 374 V. Drop-out occurs between 0.25 and 0.5 Uc (104...220 V), which is typical for AC-operated contactor coils — if your control supply dips during a motor start, the contactor may drop out before the supply recovers. Heat dissipation runs 22.8...27.8 W, so the enclosure must allow that thermal load to escape, particularly if the contactor is in a sealed cabinet. The mechanical durability of 5 million cycles and a maximum operating rate of 1800 cycles per hour at 70 °C tell you this is a standard industrial coil, not a high-speed application part.","metaTitle":"TeSys LX9FL936 Contactor Coil, 415-440 V AC/DC, Obsolete","metaDescription":"TeSys F specific contactor coil LX9FL936, 415-440 V AC 40-400 Hz low consumption. Obsolete. Sourced to order against an RFQ. 830 VA inrush, 47 VA holding.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactor & Starter Coils"],"specifications":{"Range":"TeSys","Category":"22341-CONTACTOR,D,K,&F ACCESS","Operating time":"60 ms opening 50 ms closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Heat dissipation":"22.8...27.8 W","Device short name":"LX9FL","Average resistance":"204 Ohm inrush 68 °F (20 °C) 1670 Ohm holding 68 °F (20 °C)","Inrush power in VA":"830 VA 40...400 Hz (at 68 °F (20 °C))","Control circuit type":"AC 40...400 Hz low consumption DC low consumption","Mechanical durability":"5 Mcycles","Nbr. of units in pkg.":"1","Maximum operating rate":"1800 cyc/h 158 °F (70 °C)","Product or Component Type":"Specific contactor coil","Inductance of closed circuit":"11 H","[Uc] control circuit voltage":"415...440 V AC 40...400 Hz 415...440 V DC","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.25...0.5 Uc 131 °F (55 °C))","Hold-in power consumption in VA":"47 VA 40...400 Hz (at 68 °F (20 °C))","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b8e232b776e59602f1864e6623f00d7.pdf","sourceUrl":"https://www.se.com/ie/en/product/LX9FL936/tesys-f-specific-contactor-coil-415-440-v-ac-40-400-hz-low-consumption/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LX9FL936/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LX9FL936?","answer":"There is no official successor order code documented in the lifecycle record. A functional equivalent would need to be selected based on the TeSys F contactor frame rating and the required control voltage. The key specs to match are 415...440 V AC/DC control, 830 VA inrush, 47 VA holding, and the physical mounting pattern for the TeSys F contactor."},{"question":"What is LX9FL936's listed range?","answer":"It belongs to the TeSys range, specifically the TeSys F series of contactor components."},{"question":"What is LX9FL936's category?","answer":"The category is 22341-CONTACTOR,D,K,&F ACCESS, indicating it is an accessory for contactors in the D, K, or F frame sizes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LX9FL936","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LX9FL936 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}