{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN19715","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN19715","canonicalUrl":"https://aoctrl.com/schneider/MGN19715","factsUrl":"https://aoctrl.com/api/mcp/products/MGN19715","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DCP Vigi RCBO, MGN19715, 4P, 20 A, 30 mA earth leakage, C-curve, 6 kA Icn, clip-on DIN rail.","salesMarkdown":"It combines a 20 A thermal-magnetic MCB (C-curve) with a 30 mA earth-leakage module in a single DIN-rail unit. The 30 mA sensitivity catches ground faults that could shock a person, so it's common in final subcircuits where personnel protection is needed. Breaking capacity is 6 kA Icn at 380–415 V AC per EN/IEC 61009-2-1, with a 6 kA Icu per EN/IEC 60947-2. The 4-pole body takes 8 x 9 mm pitches (72 mm wide), 85 mm tall, 76 mm deep — fits most enclosure cutouts with room for wiring. Tunnel terminals top and bottom accept 1–35 mm² rigid or 1–25 mm² flexible; strip 12 mm and torque to 2 N.m.","metaTitle":"MGN19715 Acti9 DCP Vigi RCBO, 20A, 30mA, C-curve, 6kA","metaDescription":"MGN19715 Schneider Acti9 DCP Vigi RCBO. 20A rated, 30mA earth leakage, C-curve, 6kA breaking capacity, 4P. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"76 mm","Range":"Acti9","Width":"72 mm","Colour":"Grey","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DCP Vigi","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"2","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"DCP N Vigi","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"20 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA","Number of protected poles":"4","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Non padlockable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 4.5 kA 75 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/MGN19715/acti9-dcp-n-vigi-rcbo-4p-20a-c-curve-6000a-6ka-30ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN19715/alternatives.json"},"ai":{"faq":[{"question":"What standards does MGN19715 comply with?","answer":"It complies with EN/IEC 61009-2-1 (RCBO standard) and EN/IEC 60947-2 (for the 6 kA Icu rating)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN19715","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN19715 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}