{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN19717","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN19717","canonicalUrl":"https://aoctrl.com/schneider/MGN19717","factsUrl":"https://aoctrl.com/api/mcp/products/MGN19717","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DCP Vigi RCBO, 4P, 32 A, 30 mA, C-curve, 6 kA, DIN-rail, MGN19717.","salesMarkdown":"Breaking capacity is 6 kA Icn at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1, with an Icu of 6 kA per EN/IEC 60947-2. The C-curve means the magnetic trip operates between 5 and 10 times the rated current (160–320 A for this 32 A unit), which suits mixed loads with moderate inrush — lighting banks, small motor circuits, or general socket outlets. The 30 mA earth-leakage sensitivity provides personnel protection (30 mA is the standard threshold for shock protection per IEC 60364). The tunnel-type terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable; strip 12 mm and torque to 2 N·m. Local signalling shows ON, OFF, and fault trip via the toggle. The contact position indicator confirms isolation status — the device is suitability-for-isolation rated (yes). Not padlockable, so if lockout/tagout is required, plan for an external lockable isolator upstream.","metaTitle":"MGN19717 Acti9 DCP Vigi RCBO, 32 A, 30 mA, C-curve, 4P","metaDescription":"MGN19717 Acti9 DCP Vigi RCBO, 32 A rated, 30 mA earth-leakage, C-curve, 4P, 6 kA breaking capacity. DIN-rail mount. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"76 mm","Range":"Acti9","Width":"72 mm","Colour":"Grey","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DCP Vigi","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"2","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"DCP N Vigi","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA","Number of protected poles":"4","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Non padlockable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 4.5 kA 75 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/99f96f90a1ee0edd6b8ba20ec004db72.pdf","sourceUrl":"https://www.se.com/nl/en/product/MGN19717/acti9-dcp-n-vigi-rcbo-4p-32a-c-curve-6000a-6ka-30ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN19717/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for MGN19717?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of MGN19717?","answer":"6 kA Icn at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1, with an Icu of 6 kA per EN/IEC 60947-2."},{"question":"What is the earth-leakage sensitivity of MGN19717?","answer":"30 mA, integrated into the RCBO, providing personnel shock protection per IEC 60364."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN19717","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN19717 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}