{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN19763","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN19763","canonicalUrl":"https://aoctrl.com/schneider/MGN19763","factsUrl":"https://aoctrl.com/api/mcp/products/MGN19763","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DCP Vigi RCBO, MGN19763, 13 A rated current, 30 mA earth leakage, Curve B, 10 kA breaking capacity, 2 poles, DIN rail mount.","salesMarkdown":"It combines a 13 A thermal-magnetic MCB (curve B) with integrated 30 mA earth-leakage protection in a single 36 mm wide DIN-rail module. Clip-on mounting to standard DIN rail (EN 60715). Tunnel terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible copper; strip 12 mm and torque to 2 N·m. IP20 on the body, IP40 inside the modular enclosure — fine for dry indoor distribution boards, not for washdown areas. The 13 A rating governs continuous load — size the downstream circuit for 13 A max, not the breaker's interrupt rating. The 2-pole configuration (switched and protected on both phase and neutral) is common for single-phase final subcircuits where neutral isolation is required. Tropicalisation class 2 and 95% RH at 55 °C mean it handles humid environments without derating — relevant for coastal or unconditioned plant rooms.","metaTitle":"MGN19763 Acti9 DCP Vigi RCBO, 13 A, 30 mA, Curve B, 10 kA","metaDescription":"Schneider Electric MGN19763 Acti9 DCP Vigi RCBO, 13 A rated, 30 mA earth leakage, Curve B, 10 kA breaking capacity, 2P, DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"76 mm","Range":"Acti9","Width":"36 mm","Colour":"Grey","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DCP Vigi","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"2","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"DCP H Vigi","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA","Number of protected poles":"2","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Non padlockable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 4500 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA 75 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48afceff8a6035b5f07aad0cbc3d0fbe.pdf","sourceUrl":"https://www.se.com/sg/en/product/MGN19763/acti9-dcp-h-vigi-rcbo-2p-13a-b-curve-10000a-10ka-30ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN19763/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN19763 and get a price?","answer":"The MGN19763 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is the closest alternative to MGN19763 in the Acti9 family?","answer":"The closest peer within the same Acti9 DCP Vigi family would differ only in rated current or curve code — the 13 A B-curve variant is this exact code. A different current rating (e.g., 10 A or 16 A) or curve (C or D) changes the order code; no single pin-compatible substitute exists for this specific 13 A / 30 mA / curve B combination."},{"question":"What compliance documentation does Schneider provide for MGN19763?","answer":"The MGN19763 is certified to EN/IEC 61009-2-1 and EN/IEC 60947-2. It carries CE marking for the European market. Specific RoHS/REACH declarations are available from Schneider Electric's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN19763","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN19763 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}