{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN25142","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN25142","canonicalUrl":"https://aoctrl.com/schneider/MGN25142","factsUrl":"https://aoctrl.com/api/mcp/products/MGN25142","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H Multi9 miniature circuit breaker, 4P, D curve, 6 A, 30 kA at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"The MGN25142 is a C60H miniature circuit breaker from the Multi9 range, rated 6 A at 50 °C on a 4-pole, D-curve thermal-magnetic trip. It breaks up to 30 kA Icu at 240 V AC phase-to-phase per EN/IEC 60947-2, and 15 kA at 415 V AC. That D-curve magnetic trip at 12 x In (±20%) means it handles motor inrush and transformer energization without nuisance tripping — the right choice for inductive loads on a distribution board. Occupies 8 modules of 9 mm pitch — 72 mm wide total. Depth is 73 mm, height 81 mm. IP20 finger-safe front.","metaTitle":"MGN25142 C60H MCB, 4P, D Curve, 6 A, 30 kA","metaDescription":"MGN25142 C60H miniature circuit breaker, 4 poles, D curve, 6 A rated current, 30 kA breaking capacity at 240 V AC. Active production, sourced to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"6 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/MGN25142/c60-circuit-breaker-c60h-4p-6-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN25142/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN25142 and how do I get a price?","answer":"The MGN25142 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is the closest alternative to MGN25142 in this component family?","answer":"Within the C60 range, the closest sibling is the C60N (lower breaking capacity — typically 10 kA at 415 V vs. the C60H's 15 kA). The C60H is the higher-fault-rated variant; if your fault level is lower, the C60N may be a cost-effective alternative, but verify the required Icu at your voltage."},{"question":"What is MGN25142's listed depth?","answer":"The MGN25142 has a depth of 73 mm."},{"question":"What is MGN25142's listed range?","answer":"The MGN25142 belongs to the Multi9 range, specifically the C60 product family."},{"question":"What compliance documentation does this brand provide for MGN25142?","answer":"The MGN25142 is certified to EN/IEC 60947-2. The manufacturer typically provides RoHS and REACH declarations upon request; check with your sourcing contact for specific documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN25142","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN25142 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}