{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN25147","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN25147","canonicalUrl":"https://aoctrl.com/schneider/MGN25147","factsUrl":"https://aoctrl.com/api/mcp/products/MGN25147","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, MGN25147 miniature circuit breaker, 4P, D curve, 25 A, 30 kA breaking capacity at 240 V AC.","salesMarkdown":"The MGN25147 is a 4-pole C60H miniature circuit breaker from the Schneider Electric Multi9 range, rated 25 A with a D tripping curve. It's built for distribution panels where high inrush currents — motor starts, transformer energisation, or rectifier loads — demand a curve that holds through the surge. ## Breaking capacity and what it means on your panel The MGN25147 delivers 30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V — all per EN/IEC 60947-2. The service breaking capacity Ics is 50% of those figures: 15 kA at 240 V, 7.5 kA at 415 V, and 5 kA at 440 V. Ics matters because it's the rating that tells you whether the breaker can be reused after a fault without replacement. At 72 mm wide and 8 x 9 mm pitches, it occupies four module spaces on the rail. IP20 finger protection means it's safe for open-panel mounting inside a locked cabinet; no washdown rating here.","metaTitle":"MGN25147 C60H MCB, 4P D Curve 25A, 30kA Breaking","metaDescription":"MGN25147 C60H miniature circuit breaker, 4 poles, D curve, 25 A rated current. Breaking capacity 30 kA at 240 V AC. Active production, quoted to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"25 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/MGN25147/c60-circuit-breaker-c60h-4p-25-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN25147/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN25147 and what is the lead time?","answer":"The MGN25147 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of MGN25147 at 240 V?","answer":"The breaking capacity Icu is 30 kA at 240 V AC phase-to-phase per EN/IEC 60947-2; the service breaking capacity Ics is 15 kA at the same voltage."},{"question":"What does the D curve mean on this MCB?","answer":"The D curve trips magnetically at 12 x In ±20%, making it suitable for circuits with high inrush currents such as motor starters, transformers, or discharge lighting."},{"question":"What compliance documentation does this brand provide for MGN25147?","answer":"The MGN25147 is certified to EN/IEC 60947-2 and carries IP20 protection. Pollution degree 3 is specified. The manufacturer typically provides RoHS and REACH declarations on request."},{"question":"What is the closest alternative to MGN25147 in the same family?","answer":"Within the Multi9 C60 range, the main variant differences are curve (B, C, D) and rated current. A C-curve 25 A 4P breaker (e.g., MGN25145) would share the same footprint, terminal capacity, and breaking capacity but trip magnetically at a lower multiple of In — choose it only if your load inrush is moderate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN25147","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN25147 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}