{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60526","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60526","canonicalUrl":"https://aoctrl.com/schneider/MGN60526","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60526","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 miniature circuit-breaker, MGN60526, 2-pole, D curve, 32 A rated current, 10 kA Icu at 415 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The MGN60526: Breaking capacity is listed at 20 kA Icu at 240 V AC phase-to-phase, 10 kA Icu at 415 V AC, and 6 kA Icu at 440 V AC — all per EN/IEC 60947-2. The rated service breaking capacity (Ics) is 75 % of Icu at each voltage level, so at 415 V it can clear 7.5 kA and still be usable afterward — that 75 % ratio is standard for Category A breakers (no intentional short-time delay). Two protected poles, 2P configuration, with suitability for isolation confirmed per EN/IEC 60947-2 — meaning the open contacts provide a visible air gap and the breaker is marked to serve as a disconnecting means. The contact position indicator (ON/OFF indication on the toggle) gives a positive visual confirmation of the contact state, which matters when you are locking out a circuit for maintenance. Mounts on a 35 mm symmetrical DIN rail — the standard EN 60715 profile — occupying 4 x 9 mm pitches (36 mm wide). The 73 mm depth and 81 mm height fit within the envelope of a standard distribution board or enclosure, but check the gland-plate clearance if the panel has a shallow door or a rear-mounted busbar system. Tunnel-type terminals accept 1.5 to 35 mm² conductors — flexible with or without ferrule, or solid. That 35 mm² top end means it can take a fairly heavy feeder cable for a 32 A circuit, but the terminal design is fixed, not a lug or ring-terminal type, so plan your cable termination method accordingly. The C60N series has been a workhorse in the Multi9 range for years, and the D-curve variant (MGN60526) is the one you reach for when the load has a high inrush — motor starters, small transformers, discharge lighting. If you are holding a legacy panel that uses an older C60N D32, this is the direct replacement; no adapter or busbar rework needed, provided the DIN-rail pitch and busbar spacing match. The breaker is designed for distribution duty (Category A, no intentional delay), with an electrical endurance of 10,000 cycles and mechanical endurance of 20,000 cycles. Earth-leakage protection requires a separate block (Vigi or similar) — there is no integral RCD in this unit.","metaTitle":"MGN60526 C60N Miniature Circuit-Breaker, 32 A, 2P, D Curve,","metaDescription":"MGN60526 C60N MCB from the Multi9 range. 32 A rated current, 2 poles, D tripping curve. Breaking capacity 10 kA Icu at 415 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"Power circuit: 3.5 N.m","Device application":"Distribution","[In] rated current":"32 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a270401098728af6700289336d6415eb.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60526/c60-circuit-breaker-c60n-2p-32a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60526/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60526 at 415 V?","answer":"The MGN60526 has a breaking capacity of 10 kA Icu at 415 V AC 50/60 Hz phase-to-phase, conforming to EN/IEC 60947-2. The rated service breaking capacity (Ics) at that voltage is 7.5 kA (75 % of Icu)."},{"question":"What is the D curve on this MCB?","answer":"The D curve means the magnetic trip threshold is 12 x In (±20 %), so for the 32 A rated current the instantaneous trip point is approximately 384 A. This is designed for loads with high inrush current such as motors, transformers, and discharge lighting."},{"question":"Where can I buy MGN60526 and what is the lead time?","answer":"The MGN60526 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."},{"question":"What compliance documentation does MGN60526 carry?","answer":"The MGN60526 is certified to EN/IEC 60947-2, with pollution degree 3, IP20 protection, and suitability for isolation. It is part of the Schneider Electric Multi9 range; full compliance documentation (declaration of conformity, CE marking) is available from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60526","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60526 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}