{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60530","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60530","canonicalUrl":"https://aoctrl.com/schneider/MGN60530","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60530","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60N series, MGN60530 miniature circuit breaker, 3-pole, 1 A rated current, D curve, 20 kA Icu at 240 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric MGN60530 is a C60N miniature circuit breaker from the Multi9 range — a 3-pole, 1 A rated device with a D curve, built to EN/IEC 60947-2 for distribution duty. It breaks 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V, so it handles high inrush loads like motor circuits or transformer primaries where the D curve's 12 x In magnetic trip (+/- 20%) avoids nuisance trips on startup. IP20 finger-safe for panel interiors. The 1 A rating at 50 °C (EN/IEC 60947-2) governs continuous load — this breaker protects a 1 A branch, not a motor starter. The D curve's 12 x In magnetic trip (12 A nominal, +/- 20%) means it tolerates short-duration inrush without tripping, making it a fit for control transformers, solenoid banks, or small motor loads where a C curve would nuisance-trip. Service breaking capacity (Ics) is 75% of Icu: 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V — enough for most industrial panel fault levels. Electrical durability is 10,000 cycles; mechanical, 20,000 cycles.","metaTitle":"MGN60530 C60N Miniature Circuit Breaker, 1 A D Curve, 3P","metaDescription":"MGN60530 C60N MCB, 1 A rated, D curve, 3-pole, 20 kA breaking capacity at 240 V. Active production. Sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"1 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5c1f787b72f45b91e26c33739f54eae0.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60530/c60-circuit-breaker-c60n-3p-1-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60530/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the MGN60530 and get a price?","answer":"The MGN60530 is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current availability and pricing — confirmed at quote time."},{"question":"What is the MGN60530's breaking capacity at different voltages?","answer":"It breaks 20 kA Icu at 240 V AC, 10 kA at 415 V AC, and 6 kA at 440 V AC, all phase-to-phase per EN/IEC 60947-2. Service breaking capacity (Ics) is 75% of those values."},{"question":"What does the D curve mean on this breaker?","answer":"The D curve means magnetic tripping occurs at 12 x In (+/- 20%), so this 1 A breaker trips magnetically between roughly 9.6 A and 14.4 A. It's designed for high-inrush loads like motors and transformers where a C curve would trip on startup."},{"question":"What compliance documentation does Schneider provide for the MGN60530?","answer":"The MGN60530 is certified to EN/IEC 60947-2 and carries IP20 protection. It is suitable for isolation per that standard. For specific RoHS, REACH, or UL documentation, request the compliance pack with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60530","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60530 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}