{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60531","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60531","canonicalUrl":"https://aoctrl.com/schneider/MGN60531","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60531","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 series, MGN60531, 3-pole D-curve miniature circuit breaker, 2 A rated current, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"The MGN60531 is a 3-pole C60N miniature circuit breaker from the Multi9 range, rated 2 A at 50 °C with a D tripping curve (12 x In magnetic release, +/-20 %). Breaking capacity is 20 kA Icu at 240 V AC phase-to-phase (EN/IEC 60947-2), which covers most distribution panels downstream of a 22 kA or lower transformer; at 415 V it drops to 10 kA, and at 440 V to 6 kA — so the voltage at the fault point governs whether this breaker clears without upstream backup. The thermal-magnetic trip unit is fixed — no interchangeable trip blocks. Pollution degree 3, so it's rated for the conductive-dust and humidity environment typical of industrial control panels, not just clean residential load centers. ## Integration notes Tightening torque 2 N·m on the power circuit; strip length 14 mm. The tunnel-type terminals are compatible with standard pin and fork crimp lugs. IP20 finger-safe front, so it can be mounted in a panel with exposed busbars as long as the breaker itself is guarded by the enclosure door or a separate cover.","metaTitle":"MGN60531 C60N MCB, 3P D-Curve 2A, 20kA at 240V","metaDescription":"MGN60531 C60N miniature circuit breaker, 3-pole D-curve 2A, 20kA breaking capacity at 240V AC. Sourced to order against RFQ. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"2 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ce5dea05a1f0b60c3f7f9595c5d2a7d8.pdf","sourceUrl":"https://www.se.com/th/en/product/MGN60531/c60-circuit-breaker-c60n-3p-2-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60531/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN60531?","answer":"The MGN60531 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of MGN60531 at 240 V?","answer":"The MGN60531 has a breaking capacity of 20 kA Icu at 240 V AC 50/60 Hz phase-to-phase, conforming to EN/IEC 60947-2. The service breaking capacity (Ics) at that voltage is 15 kA (75 %)."},{"question":"What standards does MGN60531 comply with?","answer":"The MGN60531 is certified to EN/IEC 60947-2 for miniature circuit breakers. It is suitable for isolation per that standard and carries a pollution degree 3 rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60531","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60531 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}