{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60532","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60532","canonicalUrl":"https://aoctrl.com/schneider/MGN60532","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60532","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60N series, MGN60532 miniature circuit breaker, 3-pole, D-curve, 3 A rated current, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"The MGN60532 is a Schneider Electric C60N miniature circuit breaker from the Multi9 range, 3-pole, D-curve, rated 3 A at 50 °C per EN/IEC 60947-2. Breaking capacity is 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V — all conforming to EN/IEC 60947-2. Rated service breaking capacity (Ics) is 75 % of Icu: 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. That's the level the breaker can clear and still be reused — important for coordination studies on distribution panels. Tightening torque 2 N·m on the power circuit; strip length 14 mm. IP20 finger-safe protection. Dimensions: 81 mm high, 54 mm wide (6 modules), 73 mm deep. The 73 mm depth is the body depth behind the panel — relevant when sizing enclosure depth or clearance for wiring ducts. Rated for isolation (suitability for isolation: Yes per EN/IEC 60947-2), with a contact position indicator and ON/OFF local signalling. Electrical durability 10,000 cycles, mechanical 20,000 cycles.","metaTitle":"MGN60532 C60N MCB, 3P D-curve 3A, 20kA/240V","metaDescription":"MGN60532 Schneider C60N miniature circuit breaker, 3-pole D-curve 3A, 20 kA breaking capacity at 240 V AC. Active production, sourced to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"3 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0caec0236ca6b7f218c3158b988d467e.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60532/c60-circuit-breaker-c60n-3p-3-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60532/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60532?","answer":"20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V, all per EN/IEC 60947-2. Service breaking capacity (Ics) is 75 % of those values."},{"question":"What does the D-curve mean on this breaker?","answer":"The D-curve magnetic trip is 12 x In ±20 %, designed for loads with high inrush current such as motors, transformers, or welding equipment. It avoids nuisance tripping on startup surges."},{"question":"What compliance documentation does Schneider provide for MGN60532?","answer":"The breaker is certified to EN/IEC 60947-2, pollution degree 3. It carries suitability for isolation marking and contact position indication. Specific RoHS/REACH/UL documentation is available from the manufacturer upon request."},{"question":"Where can I buy MGN60532 and how is it quoted?","answer":"The MGN60532 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60532","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60532 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}