{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60533","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60533","canonicalUrl":"https://aoctrl.com/schneider/MGN60533","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60533","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60N, MGN60533, 3P 4A D-curve miniature circuit breaker, 20 kA Icu at 240 V AC, 73 mm depth.","salesMarkdown":"The Schneider Electric MGN60533 is a C60N miniature circuit breaker from the Multi9 range, rated 4 A at 50 °C with a D-curve trip characteristic, 3 protected poles, and a 20 kA Icu breaking capacity at 240 V AC phase-to-phase per EN/IEC 60947-2. The D-curve trips magnetically at 12× In ±20 % (48 A to 57.6 A), which avoids nuisance tripping on capacitor bank or motor starting surges. ## Integration and compliance notes Suitability for isolation is confirmed, with a visible contact position indicator and ON/OFF local signalling. Standards compliance covers EN/IEC 60947-2, Category A (no intentional short-time delay). Separate earth-leakage protection block can be added alongside.","metaTitle":"Schneider Electric MGN60533 C60N MCB, 4A D-Curve 3P 20kA, 73","metaDescription":"Schneider Electric MGN60533 C60N Miniature Circuit Breaker, 4A rated, D-curve, 3-pole, 20kA breaking capacity at 240V. EN/IEC 60947-2. Active production. Available to order via RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"4 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/385dcd44ff43451912d19bcf1a79655f.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60533/c60-circuit-breaker-c60n-3p-4a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60533/alternatives.json"},"ai":{"faq":[{"question":"What is MGN60533's breaking capacity at different voltages?","answer":"The MGN60533 has a 20 kA Icu at 240 V AC, 10 kA Icu at 415 V AC, and 6 kA Icu at 440 V AC, all phase-to-phase per EN/IEC 60947-2. The service breaking capacity Ics is 15 kA at 240 V, 7.5 kA at 415 V, and 4.5 kA at 440 V."},{"question":"What is the D-curve trip threshold on this breaker?","answer":"The D-curve magnetic trip is set at 12× In ±20 %, so for the 4 A rating it trips magnetically between 48 A and 57.6 A. This suits loads with high inrush current like motors, transformers, or discharge lighting."},{"question":"How do I get current pricing and availability for MGN60533?","answer":"Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels. Submit a request with your target quantity and delivery window for a current quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60533","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60533 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}