{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60539","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60539","canonicalUrl":"https://aoctrl.com/schneider/MGN60539","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60539","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 miniature circuit breaker, MGN60539, 3-pole, 32 A rated, D curve, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"The Schneider Electric MGN60539 is a C60N Multi9 miniature circuit breaker — a 3-pole, 32 A thermal-magnetic MCB with a D trip curve, rated to EN/IEC 60947-2. It breaks 20 kA at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V, which covers most commercial and light industrial distribution panels where fault current stays under those thresholds. The 20 kA Icu at 240 V gives headroom for high-fault panels; the 10 kA at 415 V still suits most European 400 V distribution. Service breaking capacity (Ics) is 75 % of Icu — 15 kA at 240 V, 7.5 kA at 415 V — meaning it can reclose after a fault at that level. Snaps onto 35 mm symmetrical DIN rail, fixed mounting. Occupies 6 x 9 mm pitches (54 mm wide), so it takes six module spaces in a distribution board. Tunnel terminals accept 1.5…35 mm² rigid or flexible wire; strip 14 mm and torque to 3.5 N·m. IP20 finger-safe front, suitable for enclosed panels only.","metaTitle":"MGN60539 C60N MCB, 3P 32A D Curve, 20kA","metaDescription":"MGN60539 C60N miniature circuit breaker, 3-pole, 32 A, D curve, 20 kA breaking capacity at 240 V. Active production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"Power circuit: 3.5 N.m","Device application":"Distribution","[In] rated current":"32 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fdc4733773908b3cc75a14e4528a5e75.pdf","sourceUrl":"https://www.se.com/th/en/product/MGN60539/c60-circuit-breaker-c60n-3p-32a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60539/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN60539?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to MGN60539?","answer":"Within the same C60N Multi9 family, the closest parametric match is a 3-pole, 32 A, D-curve MCB with the same breaking capacity ratings. The exact order code differs by regional suffix or packaging variant, but the functional ratings are identical."},{"question":"What compliance documentation does MGN60539 carry?","answer":"The breaker is certified to EN/IEC 60947-2, with pollution degree 3, suitability for isolation, and IP20 protection. It carries CE marking for the European market."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60539","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60539 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}