{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60544","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60544","canonicalUrl":"https://aoctrl.com/schneider/MGN60544","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60544","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 series, MGN60544, 4-pole D-curve miniature circuit breaker, rated 2 A at 50 °C, 20 kA Icu at 240 V AC, DIN rail mount.","salesMarkdown":"Rated 2 A at 50 °C per EN/IEC 60947-2, this 4-pole breaker protects all three phases and neutral in a single module. The 20 kA Icu at 240 V AC phase-to-phase gives it the interrupting capacity to handle high-fault-current points in a panel; at 415 V the rating drops to 10 kA Icu, and at 440 V to 6 kA Icu — so the voltage at the fault point governs whether this breaker holds coordination with the upstream device. The 75 % Ics rating (15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V) tells you it can be reclosed after clearing a fault at those levels and still carry rated current — useful for a panel where you want to restore power without swapping the breaker after a downstream short. The 72 mm width (8 x 9 mm pitches) and 81 mm height fit a standard modular enclosure grid; depth of 73 mm leaves room for wiring behind the rail.","metaTitle":"MGN60544 C60N MCB, 4P D-Curve 2A, 20kA Breaking Capacity","metaDescription":"MGN60544 Schneider C60N miniature circuit breaker, 4-pole D-curve rated 2A at 50°C. 20kA Icu at 240V AC. DIN rail mount, EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"2 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/MGN60544/c60-circuit-breaker-c60n-4p-2-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60544/alternatives.json"},"ai":{"faq":[{"question":"What is MGN60544 used for?","answer":"It is a 4-pole D-curve miniature circuit breaker rated 2 A at 50 °C, used for protecting motor circuits, transformers, and other inductive loads in distribution boards where high inrush current is expected."},{"question":"Where can I buy MGN60544?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What standards does MGN60544 comply with?","answer":"It is certified to EN/IEC 60947-2, pollution degree 3, and is suitable for isolation per that standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60544","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60544 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}