{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60547","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60547","canonicalUrl":"https://aoctrl.com/schneider/MGN60547","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60547","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 series, MGN60547 miniature circuit breaker, 4-pole, D-curve, 6 A rated, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"It's a 4-pole unit with a D tripping curve and a 6 A rated current at 50 °C per EN/IEC 60947-2. Breaking capacity is 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V. The rated service breaking capacity (Ics) is 75% of Icu at each voltage level — 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. That 75% Ics/Icu ratio means after clearing a fault at rated Ics, the breaker is still functional and can be reclosed without immediate replacement. For a panel OEM, that's the difference between a quick restart and a callout to swap a welded contactor. Width is 72 mm (8 x 9 mm pitches), so it occupies four module spaces. Torque to 2 N·m on the power circuit. IP20 finger-safe protection, pollution degree 3 rated. The toggle gives local ON/OFF indication with a contact position indicator — no guessing whether it's tripped or switched off.","metaTitle":"MGN60547 C60N MCB, 4P D-Curve 6A, 20kA Breaking Capacity","metaDescription":"MGN60547 Schneider C60N Multi9 miniature circuit breaker, 4-pole D-curve, 6A rated, 20kA Icu at 240V. EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"6 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/MGN60547/c60-circuit-breaker-c60n-4p-6-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60547/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN60547 and how do I get a price?","answer":"The MGN60547 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to MGN60547 in this component family?","answer":"Within the C60 family, the closest alternative would be a C60H or C60L variant with the same pole count, curve, and current rating — the difference is breaking capacity. The C60N (MGN60547) sits at 20 kA Icu at 240 V; a C60H would offer higher interrupting capacity, while a C60L would be a lower-cost option for lower fault-current installations. Pinout and footprint are identical across the C60 series."},{"question":"What is MGN60547's listed depth?","answer":"The MGN60547 has a depth of 73 mm."},{"question":"What compliance documentation does this brand provide for MGN60547?","answer":"The MGN60547 is certified to EN/IEC 60947-2, with pollution degree 3 and IP20 protection. It carries Schneider Electric's standard declarations of conformity for the European market. Specific RoHS, REACH, and UL documentation should be requested at quote time to confirm current compliance status."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60547","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60547 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}