{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60615","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60615","canonicalUrl":"https://aoctrl.com/schneider/MGN60615","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60615","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H Multi9 series, MGN60615, 1-pole miniature circuit breaker, 20 A rated, C-curve, 15 kA Icu at 240 V AC, 24 kA Icu at 60 V DC, DIN rail mount.","salesMarkdown":"The MGN60615 is a 1-pole C60H miniature circuit breaker from the Multi9 range, rated 20 A at 50 °C per EN/IEC 60947-2. The C-curve (magnetic trip at 8.5 x In, +/- 20 %) means it holds brief motor inrush but trips fast on a hard short; it's the standard choice for general-purpose distribution and mixed resistive-inductive loads in a control panel. Breaking capacity is 15 kA Icu at 240 V AC phase-to-neutral, and 24 kA Icu at 60 V DC phase-to-phase. The 24 kA DC rating is unusually high for a 1-pole 20 A MCB; it means this breaker handles battery-bank or rectifier-fed DC bus faults where most residential-grade MCBs would fail. Snaps onto a 35 mm symmetrical DIN rail, 18 mm wide (2 x 9 mm pitches). That 18 mm width is the standard single-module footprint for a 1-pole MCB — it occupies one slot in a distribution board or enclosure rail. Tunnel terminals accept 1 to 25 mm² rigid or flexible wire; strip 14 mm and torque to 2 N·m. Suitable for isolation — the contact position indicator shows ON/OFF status visually. Mechanical durability is 20,000 cycles; electrical durability 10,000 cycles at rated load. Ambient operating range is -30 to 70 °C, storage -40 to 80 °C. Earth-leakage protection requires a separate block (not built-in).","metaTitle":"MGN60615 C60H MCB, 20A 1P C-Curve, 15kA/24kA Breaking Capaci","metaDescription":"MGN60615 Schneider C60H MCB, 20A rated, 1-pole C-curve. 15 kA Icu at 240 V AC, 24 kA at 60 V DC. EN/IEC 60947-2. DIN rail mount. Available to order, quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 24 kA Icu at 60 V DC phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Poles description":"1P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"20 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"240 V AC 50/60 Hz phase to neutral 415 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 2 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 24 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/09894f16dd2f750e579d3cb3e0833b98.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60615/c60-circuit-breaker-c60h-1p-20a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60615/alternatives.json"},"ai":{"faq":[{"question":"What is MGN60615's breaking capacity at 240 V AC?","answer":"15 kA Icu at 240 V AC phase-to-neutral per EN/IEC 60947-2. Service breaking capacity (Ics) is 7.5 kA at the same voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60615","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60615 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}