{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60639","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60639","canonicalUrl":"https://aoctrl.com/schneider/MGN60639","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60639","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H Multi9 miniature circuit-breaker, 3-pole, 10 A, curve C, 30 kA Icu at 240 V AC, EN/IEC 60947-2, IP20, 35 mm DIN rail.","salesMarkdown":"## Integrator note — C60H 3P 10 A curve C The MGN60639 is a C60H miniature circuit-breaker from the Multi9 range, rated 10 A at 50 °C per EN/IEC 60947-2, with a C curve (magnetic trip at 8.5 x In ±20 %). Three protected poles, thermal-magnetic trip unit, suitable for isolation. The Ics (service breaking capacity) is 50 % of Icu at AC voltages — 15 kA at 240 V AC, 7.5 kA at 415 V AC, 5 kA at 440 V AC — and 40 kA (100 %) at 125 V DC. That DC rating makes it a candidate for battery-bank or UPS output protection where high interrupting capacity is needed. ## Panel integration — DIN rail and wiring Occupies 6 x 9 mm pitches (54 mm wide). Comb busbar compatible top or bottom. IP20 finger-safe for enclosed panel use. Listed as current-production lifecycle stage. Fully compliant with EN/IEC 60947-2 (Category A). Electrical endurance rated 10,000 cycles, mechanical 20,000 cycles. Ambient operating range -30…70 °C, storage -40…80 °C. Earth-leakage protection requires a separate Vigi block — not integrated.","metaTitle":"MGN60639 C60H MCB, 3P 10A Curve C, 30 kA, Multi9","metaDescription":"MGN60639 C60H miniature circuit-breaker, 3-pole 10 A, curve C, 30 kA breaking capacity at 240 V AC. Active lifecycle, EN/IEC 60947-2 compliant. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"10 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 40 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e6bb208d3ebed146333e50aacc3c9f68.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60639/c60-circuit-breaker-c60h-3p-10a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60639/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60639 at 240 V AC?","answer":"30 kA Icu at 240 V AC 50/60 Hz phase-to-phase per EN/IEC 60947-2. The Ics at that voltage is 15 kA (50 %)."},{"question":"What is the closest alternative to MGN60639 in the same family?","answer":"Within the C60 range, the standard C60 (non-H) offers lower breaking capacity — typically 10 kA or 15 kA at 240 V AC — versus the C60H's 30 kA. The C60H is the high-interrupting variant; if your fault level is below 15 kA, a C60 may suffice, but verify coordination with your upstream device."},{"question":"Where can I buy MGN60639 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60639","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60639 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}