{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60640","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60640","canonicalUrl":"https://aoctrl.com/schneider/MGN60640","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60640","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, MGN60640 miniature circuit breaker, 16 A rated current, C curve, 3 poles, 30 kA breaking capacity at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"The MGN60640 is a C60H miniature circuit breaker from the Multi9 range, rated 16 A at 50 °C with a C curve (magnetic trip at 8.5 x In ±20 %). Three poles, so it switches all three phases in a 3-phase distribution board. Thermal-magnetic trip unit gives both overload (thermal) and short-circuit (magnetic) protection in one device. Snaps onto 35 mm symmetrical DIN rail — standard for any European-style distribution board or sub-panel. Fixed mounting, toggle control, ON/OFF indication on the front. IP20 finger-safe terminals accept 1–25 mm² rigid or flexible cable; tunnel terminals with 2 N·m tightening torque. 6 module pitches (54 mm wide) means it takes up six 9 mm slots on the rail — plan your busbar and comb-bridge accordingly. Pollution degree 3 (industrial environment). Suitable for isolation per the standard — the contact position indicator confirms open/closed state. Utilisation category A (non-selectivity required). Electrical durability 10,000 cycles, mechanical 20,000 cycles.","metaTitle":"MGN60640 C60H MCB 16A C Curve 3P 30kA, Multi9","metaDescription":"MGN60640 C60H miniature circuit breaker, 16 A rated current, C curve, 3 poles, 30 kA breaking capacity at 240 V AC. Active production, sourced to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"16 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 40 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0be06f6b800faadfa549565dae9debc8.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60640/c60-circuit-breaker-c60h-3p-16a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60640/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60640?","answer":"30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V AC, 10 kA at 440 V AC, and 25 kA at 125 V DC, all per EN/IEC 60947-2."},{"question":"What is the closest alternative to MGN60640 in the same family?","answer":"Within the C60H series, the same 16 A C curve 3P rating is available; the key difference is breaking capacity — the C60H (MGN60640) offers 30 kA at 240 V AC, while the standard C60 is typically 10 kA or 15 kA. Choose based on your fault level."},{"question":"Where can I buy MGN60640?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60640","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60640 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}