{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60651","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60651","canonicalUrl":"https://aoctrl.com/schneider/MGN60651","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60651","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H Multi9 miniature circuit breaker, MGN60651, 6 A rated current, C-curve, 4-pole, 30 kA Icu at 240 V AC, thermal-magnetic trip, EN/IEC 60947-2.","salesMarkdown":"The MGN60651 is a 6 A C-curve 4-pole miniature circuit breaker from the Schneider C60H series (Multi9 range), rated for distribution duty under EN/IEC 60947-2. The 30 kA Icu at 240 V AC phase-to-phase means it safely interrupts faults up to 30 kA at that voltage; at 415 V AC the rating drops to 15 kA, and at 440 V AC to 10 kA. For DC circuits, the 50 kA Icu at 250 V DC is the figure to use. The 4-pole configuration protects all four conductors in a three-phase-plus-neutral system; the fourth pole is switched, not just neutral disconnection. The 72 mm width occupies 8 x 9 mm pitches — standard for a 4P MCB in the Multi9 family. Strip length is 14 mm. IP20 finger-safe terminals are fine for enclosed panels; no washdown rating. Comb busbar compatible top or bottom.","metaTitle":"MGN60651 C60H MCB, 6 A C-curve 4P, 30 kA at 240 V AC","metaDescription":"MGN60651 Schneider C60H MCB, 6 A, C-curve, 4-pole, 30 kA Icu at 240 V AC. Active production, EN/IEC 60947-2. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 50 kA Icu at 250 V DC phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"6 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 250 V DC 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 250 V DC","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0a14ea3e39d50c6c87d1d587e78c6ef4.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60651/c60-circuit-breaker-c60h-4p-6a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60651/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN60651 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is MGN60651's listed depth (73 mm) on this component line?","answer":"The depth is 73 mm, which is standard for the C60H 4P footprint on a DIN rail."},{"question":"What is MGN60651's listed range (Multi9) on this component line?","answer":"The range is Multi9, the legacy residential and commercial MCB/RCBO family from Schneider Electric."},{"question":"What compliance documentation does this brand provide for MGN60651 (RoHS, REACH, UL, IEC)?","answer":"The breaker is certified to EN/IEC 60947-2. Pollution degree 3 per that standard. For RoHS/REACH declarations and UL listing, refer to the manufacturer's compliance documentation available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60651","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60651 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}