{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60652","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60652","canonicalUrl":"https://aoctrl.com/schneider/MGN60652","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60652","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, MGN60652, 4-pole miniature circuit-breaker, C-curve, 10 A rated current, 50 kA Icu at 250 V DC, thermal-magnetic trip, EN/IEC 60947-2.","salesMarkdown":"The MGN60652 is a 4-pole C60H miniature circuit-breaker from the Multi9 range, rated 10 A at 50 °C per EN/IEC 60947-2. On AC, Icu is 30 kA at 240 V and 15 kA at 415 V, with Ics at 50% of those values — the breaker survives the fault and can be reclosed after a downstream short. The 4-pole configuration with separate earth-leakage block compatibility means you can add RCD protection via a companion module without swapping the breaker. ## Integration notes The toggle actuator provides local ON/OFF indication and a contact position indicator for visual confirmation of isolation status — suitable for lockout/tagout verification. IP20 finger-safe terminals, so it's panel-mount only, not field-exposed.","metaTitle":"MGN60652 C60H Miniature Circuit-Breaker, 4P, C-Curve, 10 A,","metaDescription":"MGN60652 C60H MCB, 4 poles, C-curve, 10 A rated current. Breaking capacity 50 kA at 250 V DC. EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 50 kA Icu at 250 V DC phase to phase conforming to EN/IEC 60947-2","Device short name":"C60H","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"10 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 250 V DC 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 250 V DC","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0c254be518c15f42143745adf9c66414.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60652/c60-circuit-breaker-c60h-4p-10a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60652/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60652 at 250 V DC?","answer":"The MGN60652 has a breaking capacity of 50 kA Icu at 250 V DC (phase-to-phase), conforming to EN/IEC 60947-2. That is the highest DC rating in its class — important for DC distribution or battery-backed circuits."},{"question":"Where can I buy MGN60652?","answer":"The MGN60652 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What compliance documentation does MGN60652 carry?","answer":"The MGN60652 is certified to EN/IEC 60947-2 (pollution degree 3, category A). It carries CE marking for the European market. For specific RoHS/REACH/UL documentation, request the manufacturer's declaration at order time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60652","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60652 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}