{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60885","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60885","canonicalUrl":"https://aoctrl.com/schneider/MGN60885","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60885","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, Multi9 C60 series, C60N miniature circuit-breaker, MGN60885, 2-pole C-curve 40 A, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"The MGN60885 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, a 2-pole (2P) thermal-magnetic device rated 40 A at 50 °C per EN/IEC 60947-2. The C-curve trips magnetically at 8.5 x In (±20 %), so it holds through motor inrush and transformer energisation but clears a hard short inside half a cycle — the right characteristic for distribution circuits feeding mixed inductive and resistive loads, provided the downstream coordination study respects the 20 kA Icu at 240 V AC phase-to-phase. It is also rated for isolation, meaning the open contacts give a verifiable air gap that holds the unit on the grid during a lockout-tagout. Breaking capacity follows the voltage: 20 kA Icu at 240 V AC, 10 kA at 415 V AC, 6 kA at 440 V AC — all phase-to-phase per EN/IEC 60947-2. For a 400/415 V distribution panel that means the MGN60885 coordinates downstream of a 25 kA-rated main breaker, provided the let-through energy of the upstream device stays below the 10 kA withstand of this pole. The 4-module width (36 mm, 4 x 9 mm pitches) fits standard DIN-rail enclosures without crowding the busbar feed. Snaps onto 35 mm symmetrical DIN rail, fixed mounting only — no plug-in base. Tunnel-type terminals accept 1.5 to 35 mm² rigid or flexible (with or without ferrule); strip length is 14 mm, torque to 3.5 N·m. The IP20 finger-safe front is standard for enclosed panels; pollution degree 3 per EN/IEC 60947-2 means it tolerates conductive dust in industrial environments, provided the enclosure maintains the rated clearance. Comb busbars feed top or bottom. A separate earth-leakage block (Vigi) can be added on the load side for residual-current protection. ## Environmental range and durability Operates from -30 to 70 °C, stores from -40 to 80 °C — wide enough for unheated electrical rooms and outdoor enclosures in temperate climates. Mechanical endurance is 20,000 cycles; electrical endurance is 10,000 cycles at rated current per EN/IEC 60947-2, which for a distribution MCB in a panel that cycles infrequently translates to decades of service life. The toggle gives a local ON/OFF indication and the contact position indicator confirms the state without removing the cover.","metaTitle":"MGN60885 C60N MCB, 2P C-Curve 40 A, 20 kA Breaking","metaDescription":"Schneider Electric MGN60885 C60N miniature circuit-breaker, 2-pole C-curve 40 A, 20 kA Icu at 240 V AC. EN/IEC 60947-2. Active production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"2P","Tightening torque":"Power circuit: 3.5 N.m","Device application":"Distribution","[In] rated current":"40 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f00ed7ce266dc5dc3817c941faba9a4f.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60885/c60-circuit-breaker-c60n-2p-40a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60885/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN60885 and what is the lead time?","answer":"The MGN60885 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to MGN60885 in the same family?","answer":"Within the Multi9 C60 range, the closest alternative is a 2-pole C60N with the same C-curve but a different rated current — for example, a 32 A or 50 A variant. The footprint, breaking capacity, and terminal range are identical; only the thermal trip rating changes."},{"question":"What compliance documentation does Schneider provide for MGN60885?","answer":"The MGN60885 is certified to EN/IEC 60947-2, which covers the breaking capacity, service capacity, and isolation suitability. It carries CE marking for the European market and is suitable for isolation per the standard. RoHS and REACH compliance is standard for the Multi9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60885","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60885 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}