{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60888","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60888","canonicalUrl":"https://aoctrl.com/schneider/MGN60888","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60888","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 miniature circuit-breaker, MGN60888, 3 poles, 1 A rated current, C curve, 20 kA Icu at 240 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The MGN60888 is a 3-pole C60N miniature circuit-breaker from the Multi9 range, rated 1 A at 50 °C per EN/IEC 60947-2. The 20 kA Icu at 240 V AC phase-to-phase gives headroom for high-fault panels; at 415 V AC the breaking capacity is 10 kA Icu, and at 440 V AC it drops to 6 kA Icu — so the voltage class of your supply determines the available fault-clearing capability. This is a Category A breaker (no intentional short-time delay), so it's suited for branch-circuit protection where selectivity with upstream devices relies on current-limiting performance rather than time grading. The thermal-magnetic trip unit provides overload protection via the bimetal element and short-circuit protection via the solenoid — no electronic adjustment, so set it and forget it. The 3-pole body occupies 6 x 9 mm pitches (54 mm wide), 81 mm tall, 73 mm deep — standard footprint for a Multi9 C60N. IP20 finger-safe terminals suit enclosed panel use.","metaTitle":"MGN60888 C60N MCB, 3P, 1 A, C Curve, 20 kA Icu","metaDescription":"MGN60888 C60N miniature circuit-breaker, 3 poles, 1 A rated current, C curve, 20 kA Icu at 240 V AC. EN/IEC 60947-2, DIN rail mount. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"1 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a600a729ab3217fe435ac328ed226919.pdf","sourceUrl":"https://www.se.com/sg/en/product/MGN60888/c60-circuit-breaker-c60n-3p-1a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60888/alternatives.json"},"ai":{"faq":[{"question":"What is MGN60888's breaking capacity at different voltages?","answer":"The MGN60888 has a breaking capacity (Icu) of 20 kA at 240 V AC, 10 kA at 415 V AC, and 6 kA at 440 V AC, all phase-to-phase per EN/IEC 60947-2. The Ics (service breaking capacity) is 75% of Icu at each voltage level."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60888","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60888 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}